2. Installation
PNEG-1813
Electronic Distributor Control
21
Wire and Fitting Selection Recommendations
NOTE:
The power cable, encoder cable, proximity sensor cables, motor cable, and electrical fittings are
not supplied with the electronic distributor control. The following recommendations should be followed
when selecting wire types and electrical fittings:
For the proximity sensor and encoder cables from the junction box to the control panel, use 10 conductor
or greater shielded cable, 22 AWG or larger, and rated for the environment. If the wiring is run outside of
conduit, it should be rated for UV.
For the motor cable from the motor to the control panel, use 4 conductor cable, shielded, 16 AWG or
larger, and rated for the environment. If the wiring is run outside of conduit, it should be rated for UV.
All conduit and fittings should be outdoor-rated to keep things adequately sealed.