CONTROLLO ZONE FZ4B
116
cod. FZ4B - 06/2011 (Rev. 00)
EN
"TS" - TRANSPARENT PARAMETERS MENU
The zone controller is equipped with 38 transparent parameters also modi
fi
able from Remote Control (Service Menu):
Com.Rem. Board FZ4B
Boiler Board
(If arr.)
Description of Transparent Parameters
Range
Default
01
P01
Zone1 Min. Temperature
20-90°C
20°C
02
P02
Zone1 Max. Temperature
20-90°C
40°C
03
P03
Zone1 calculated setpoint offset
0-40°C
10°C
04
P04
Not implemented
10-90°C
90°C
05
P05
o01
Zone1 External Probe Curve
0-10
0
06
P06
o02
Zone1 External Probe Offset
20-40°C
30°C
07
P07
Zone2 Min. Temperature
20-90°C
20°C
08
P08
Zone2 Max. Temperature
20-90°C
40°C
09
P09
Zone2 calculated set point offset
0-40°C
0°C
10
P10
Not implemented
10-90°C
90°C
11
P11
o03
Zone2 External Probe Curve
0-10
0
12
P12
o04
Zone2 External Probe Offset
20-40°C
30°C
13
P13
Zone3 Min. Temperature
20-90°C
20°C
14
P14
Zone3 Max. Temperature
20-90°C
80°C
15
P15
Zone3 calculated setpoint offset
0-40°C
0°C
16
P16
Not implemented
10-90°C
90°C
17
P17
o05
Zone3 External Probe Curve
0-10
0
18
P18
o06
Zone3 External Probe Offset
20-40°C
30°C
19
P19
Mixing valve on+off time (Only for Mixed Zones)
0-15sec
15
20
P20
Mixing valve Boost (Only for Mixed Zones)
0-120sec
0sec
21
P21
Mixing valve on+off time for °C (Only for Mixed Zones)
00-15°C/sec 1sec/°C
22
P22
Hot water tank hysteresis
0-20°C
4°C
23
P23
Hot water tank Primary setpoint (Excluding “Stand Alone 1” con
fi
gurations)
70-85°C
80°C
24
P24
Pump start temperature (Excluding “Stand Alone 1” con
fi
gurations)
0-60°C
0°C
25
P25
Hot water tank priority
0=Off, 1=On 0=Off
26
P26
Hot water tank setpoint (Only without Remote Control)
10-65°C
55°C
27
P27
Post-circulation time
0-20min
10min
28
P28
Zone pumps status with boiler in DHW mode (Only for "Communicating" con
fi
gurations with DHW)
0=Off, 1=On 0=Off
29
P29
Delay for Zone
0-255sec
30sec
30
P30
Equal settings for each zone
0=Off, 1=On 0=Off
31
P31
Mixing valve Closing time
0-3min
3min
32
P32
Heating hysteresis (Only for “Stand Alone 2” con
fi
gurations)
0-10°C
5°C
33
P33
Heating standby time (Only for “Stand Alone 2” con
fi
gurations)
0-10min
2min
34
P34
Pump activation with card in standby
0=Off, 1=On 0=Off
35
P35
Heating delivery probe enabling (Only for “Stand Alone 2” con
fi
gurations)
0=Off, 1=On 0=Off
36
P36
Operation with boiler in fault status
0=Off, 1=On 0=Off
37
P37
Legionella protection
0=Off, 1-7
0=Off
38
P38
Boiler Summer/Winter mode
0=On, 1=Off 0=On
Press the + and - buttons to scroll the list of parameters in increasing or decreasing order respectively. To modify the value of a parameter, just press the Ok button after
selecting it: press the + and - buttons to modify it; the setting will be automatically saved. Press the Ok button to return to the list of parameters. Press the Ok button for 3
seconds to return to the Service Menu. Press the Ok button for 5 seconds to exit the card Service Menu, or exiting occurs automatically after 15 minutes.
"IN” - INFORMATION MENU
The card can display the following information:
t01
NTC sensor (T1)
between 05 and 125 °C
t02
NTC sensor (T2)
between 05 and 125 °C
t03
NTC sensor (T3)
between 05 and 125 °C
t04
NTC sensor (T4)
between -30 and 70°C (Negative values
fl
ash)
t05
On/Off Thermostat request or Room temperature measured by Remote Control (RT1)
ON/OFF or between 05 and 125 °C
t06
On/Off Thermostat request or Room temperature measured by Remote Control (RT2)
ON/OFF or between 05 and 125 °C
t07
On/Off Thermostat request or Room temperature measured by Remote Control (RT3)
ON/OFF or between 05 and 125 °C
t08
Zone1 Heating set point (Calculation)
between 05 and 125 °C
t09
Zone2 Heating set point (Calculation)
between 05 and 125 °C
t10
Zone3 Heating set point (Calculation)
between 05 and 125 °C
t11
Zone Card Heating set point (Calculation)
between 05 and 125 °C
Press the + and - buttons to scroll the list of information in increasing or decreasing order respectively. To display the value of a parameter, press the Ok button after
selecting it: in case of damaged Sensor, the card will display hyphens. Press the Ok button to return to the list of parameters. Press the Ok button for 3 seconds to return
to the Service Menu. Press the Ok button for 5 seconds to exit the card Service Menu, or exiting occurs automatically after 15 minutes.
"HI" - HISTORY MENU
The card can store the last 10 faults: the History datum item H1 represents the most recent fault that occurred, whereas the History datum item H10 represents the least recent.
The codes of the faults saved are also displayed in the corresponding menu of the Remote Control.
Press the + and - buttons to scroll the list of faults. To display the value of a parameter, press the Ok button after selecting it.
Press the Ok button for 3 seconds to return to the Service Menu. Press the Ok button for 5 seconds to exit the card Service Menu, or exiting occurs automatically after 15
minutes.