CONTROLLO ZONE FZ4B
104
cod. FZ4B - 06/2011 (Rev. 00)
EN
culated from Remote Control.
6.9 “TWO MIXED ZONES – NO EXTERNAL SENSOR”
Autocon
fi
guration:
Connection
Description
7
Pump phase (RY1)
Mixed zone 1
8
Pump neutral (RY1)
Mixed zone 1
8
Pump neutral (RY4)
Mixed zone 2
9
Mixing Valve Opening phase (RY2)
Mixed zone 1
10
Mixing Valve neutral (RY2)
Mixed zone 1
11
Mixing Valve Closing phase (RY3)
Mixed zone 1
12
Pump phase (RY4)
Mixed zone 2
13
Mixing Valve Opening phase (RY5)
Mixed zone 2
14
Mixing Valve neutral (RY5)
Mixed zone 2
15
Mixing Valve Closing phase (RY6)
Mixed zone 2
19
On/Off Thermostat or Remote Control (RT1)
Mixed zone 1
20
On/Off Thermostat or Remote Control (RT1)
Mixed zone 1
21
On/Off Thermostat or Remote Control (RT2)
Mixed zone 2
22
On/Off Thermostat or Remote Control (RT2)
Mixed zone 2
25
NTC sensor (T1)
Mixed zone 1 delivery
26
NTC sensor (T1)
Mixed zone 1 delivery
27
NTC sensor (T2)
Mixed zone 2 delivery
28
NTC sensor (T2)
Mixed zone 2 delivery
29
NTC sensor (T3)
Heating delivery
30
NTC sensor (T3)
Heating delivery
X15
Card SK connected
The algorithm remains the same as the con
fi
guration: 6.7 “ONE Mixed Zone – No External Sensor”.
What changes is:
a. The calculation of Zone card Heating Setpoint
In case of simultaneous request, the Zone card Heating Setpoint is equal to the higher of the two: Zone1 Heating Setpoint and Zone2 Heating Setpoint.
If the zone that ends the request has the higher Heating Setpoint, the Zone card Heating Setpoint must be immediately decreased until it is equal to the Heating
Setpoint of the zone still in request status.
If the zone that starts the request has a higher Heating Setpoint than the zone already in request status, the Zone card Heating Setpoint must be immediately increased
until it is equal to the higher Heating Setpoint of the zone in request status.
b. Each zone has its own adjustment sensors and parameters.
c. Post-circulation time
This must be carried out only on the last zone that ends the request.
Also, if the last zone in request status is doing post-circulation and another zone starts its own request, post-circulation must be stopped whereas the mixing valve
must be closed for the entire duration of the Mixing valve closing Time timer (TSP31): so that there is always and only a single zone in post-circulation.
6.10 “TWO MIXED ZONES – WITH EXTERNAL SENSOR”
Autocon
fi
guration:
Connection
Description
7
Pump phase (RY1)
Mixed zone 1
8
Pump neutral (RY1)
Mixed zone 1
8
Pump neutral (RY4)
Mixed zone 2
9
Mixing Valve Opening phase (RY2)
Mixed zone 1
10
Mixing Valve neutral (RY2)
Mixed zone 1
11
Mixing Valve Closing phase (RY3)
Mixed zone 1
12
Pump phase (RY4)
Mixed zone 2
13
Mixing Valve Opening phase (RY5)
Mixed zone 2
14
Mixing Valve neutral (RY5)
Mixed zone 2
15
Mixing Valve Closing phase (RY6)
Mixed zone 2
19
On/Off Thermostat or Remote Control (RT1)
Mixed zone 1
20
On/Off Thermostat or Remote Control (RT1)
Mixed zone 1
21
On/Off Thermostat or Remote Control (RT2)
Mixed zone 2
22
On/Off Thermostat or Remote Control (RT2)
Mixed zone 2
25
NTC sensor (T1)
Mixed zone 1 delivery
26
NTC sensor (T1)
Mixed zone 1 delivery
27
NTC sensor (T2)
Mixed zone 2 delivery
28
NTC sensor (T2)
Mixed zone 2 delivery
29
NTC sensor (T3)
Heating delivery
30
NTC sensor (T3)
Heating delivery
30
NTC sensor (T4)
External probe
31
NTC sensor (T4)
External probe
X15
Card SK connected
The algorithm remains the same as the con
fi
guration: 6.9 “TWO Mixed Zones – No External Sensor”.
What changes is only the calculation of Zone1 Heating Setpoint and Zone2 Heating Setpoint if the sliding temperature was activated in one or both zones.
Summary of Contents for FZ4B
Page 292: ......