CONTROLLO ZONE FZ4B
110
cod. FZ4B - 06/2011 (Rev. 00)
EN
restart with the normal algorithm.
b. DHW does not have priority over Heating: the Hot water tank Priority parameter (TSP25) is equal to 1.
In case of simultaneous request, the Zone card Heating Setpoint is equal to the highest of the three: Zone1 Heating Setpoint, Zone2 Heating Setpoint and Hot water
tank Primary Setpoint (TSP23).
If the circuit (Heating or Hot water tank) that ends the request has the highest Setpoint, the Zone card Heating Setpoint must be immediately decreased until it is
equal to the Setpoint of the circuit (Heating or Hot water tank) still in request status.
If the circuit (Heating or Hot water tank) that starts the request has a higher Setpoint than the circuit already in request status, the Zone card Heating Setpoint must
be immediately increased until it is equal to the higher Setpoint of the circuit (Heating or Hot water tank) in request status.
c. Each zone has its own adjustment parameters.
d. Post-circulation time
During DHW mode, if the pump of the zone is doing post-circulation, the latter must be stopped. At the end of DHW mode, post-circulation must not restart.
6.20.2 Remote Control
The algorithm of the Direct zones remains the same as the con
fi
guration: 6.3 “TWO Direct Zones – No External Sensor”.
The algorithm of the Hot water tank remains the same as the con
fi
guration: 6.17 “ONE Hot water tank".
What changes is:
a. DHW has priority over Heating: the Hot water tank Priority parameter (TSP25) is equal to 0.
During DHW mode, the algorithm of the Hot water tank has the highest priority.
During DHW mode, the zone request (if occurring) must be stopped without doing post-circulation. At the end of DHW mode, the zone request (if occurring) must
restart with the normal algorithm.
b. DHW does not have priority over Heating: the Hot water tank Priority parameter (TSP25) is equal to 1.
In case of simultaneous request, the Zone card Heating Setpoint is equal to the highest of the three: Zone1 Heating Setpoint, Zone2 Heating Setpoint and Hot water
tank Primary Setpoint (TSP23).
If the circuit (Heating or Hot water tank) that ends the request has the highest Setpoint, the Zone card Heating Setpoint must be immediately decreased until it is
equal to the Setpoint of the circuit (Heating or Hot water tank) still in request status.
If the circuit (Heating or Hot water tank) that starts the request has a higher Setpoint than the circuit already in request status, the Zone card Heating Setpoint must
be immediately increased until it is equal to the higher Setpoint of the circuit (Heating or Hot water tank) in request status.
c. Each zone has its own adjustment parameters.
d. Post-circulation time
During DHW mode, if the pump of the zone is doing post-circulation, the latter must be stopped. At the end of DHW mode, post-circulation must not restart.
e. DHW setpoint
The range for management of ID56 of the Remote Controls (DHW temperature adjustment button) is between 10°C and 65°C: zone card
fi
xed ranges.
Modi
fi
cation of the DHW Setpoint occurs in parallel: through the Hot water tank Setpoint parameter (TSP26) or through ID56 of the Remote Controls; the zone card
takes the last modi
fi
ed value and must update the others.
f. DHW Eco/Comfort (1 Remote Control)
In Economy mode the DHW request generated by T2 is disabled.
In Comfort mode the DHW request generated by T2 is enabled.
g. DHW Eco/Comfort (plus 1 Remote Control)
The DHW request generated by T2 is enabled only if all the Remote Controls are in Comfort mode.
6.21 “TWO DIRECT ZONES AND ONE HOT WATER TANK – WITH EXTERNAL SENSOR”
Autocon
fi
guration:
Connection
Description
7
Pump phase or Valve (RY1)
Direct zone 1
8
Pump neutral or Valve (RY1)
Direct zone 1
10
Pump neutral or Valve (RY2)
Direct zone 2
12
Pump phase or Valve (RY4)
Direct zone 2
14
Pump neutral (RY7)
Hot water tank
16
Pump phase (RY7)
Hot water tank
19
On/Off Thermostat or Remote Control (RT1)
Direct zone 1
20
On/Off Thermostat or Remote Control (RT1)
Direct zone 1
11
On/Off Thermostat or Remote Control (RT2)
Direct zone 2
22
On/Off Thermostat or Remote Control (RT2)
Direct zone 2
27
NTC sensor (T2)
Hot water tank probe
28
NTC sensor (T2)
Hot water tank probe
29
NTC sensor (T3)
Heating delivery
30
NTC sensor (T3)
Heating delivery
30
NTC sensor (T4)
External probe
31
NTC sensor (T4)
External probe
X15
Card SK connected
The algorithm remains the same as the con
fi
guration: 6.20 “TWO Direct Zones and ONE Hot water tank – No External Sensor”.