Smart SVC Relay Instruction Manual
25
Figure 3.33
With the message in
Figure 3.34, the
device starts current transformer test by activating the
first three stages.
Figure 3.34
If the connections are correct, the information about completion of the first test is given to the
user after the message in
Figure 3.35.
Figure 3.35
NOTE
:
“+”and “-” values on the right side of L1, L2, L3 states current transformer connection
directions. In the example, “-”displaying next to “L2” indicated the current transformer
direction that is attached to the relevant phase is reversed. SMART SVC RELAY realizes this
situation and fix the reverse connection automatically.
NOTE
:
If the current drawn by activated stages is insufficient, Smart relay increases the
number of activated stages and continues the test.
NOTE
:
In order for SMART SVC RELAY to complete current transformer test in a short time,
it is advised to place three-phase capacitors to the first stages from large to small. Connecting
two-phase, single-phase capacitors and constant shunt reactors to the next stages enables
transformer test to be completed in a short time. It is not compulsory to carry out this advice.
Even though stage connections are not done like above, Smart relay will complete the test and
start to operate correctly. In addition to this, it is recommended that the current transformer
used in the system have a class of 0.5 for measurement accuracy.
After the first completed transformer test, the following message (
Figure 3.36
) will display on
the screen and the current transformer test repeats for control.
Figure 3.36
After the repeated current transformer test, the message in
Figure 3.37 informs
the user about
current transformer directions and the process completed by receiving the message in
Figure
3.38
.
Transformer Control
1
Load must be constant
L1 - L2 - L3 -
L1 + L2 - L3 +
Transformer Control 2
Load must be constant
L1 + L2 - L3 +
L1 + L2 - L3 +
Transformer Control
Process completed
Summary of Contents for SMART GES1
Page 10: ...Smart SVC Relay Instruction Manual 10 1 4 1 SMART S12 1 4 Connection Diagrams...
Page 11: ...Smart SVC Relay Instruction Manual 11 1 4 2 SMART S18...
Page 12: ...Smart SVC Relay Instruction Manual 12 1 4 3 SMART S18 T...
Page 13: ...Smart SVC Relay Instruction Manual 13 1 4 4 SMART SOG1 SOG5...
Page 14: ...Smart SVC Relay Instruction Manual 14 1 4 5 SMART GES1 GES5...