5.3.2 Map of main menu and service menu 1
Fig. 12
Map of main menu and service menu 1
• "
VOLTAGE ALARM
", "
ALARM TIMER
" and "
AIR FLOW
" will be factory-set at final assembly test but may need to be altered upon
commissioning.
• "
TANK HEIGHT
" will need to be set specifically to the application, and will need to be entered upon commissioning.
• "
PRODUCTION
START
/
STOP
", and "
TANK ALARM
" will need to be set specifically to the customer's requirements.
TM
04
1
505
47
11
ALT
OK
OK
OK
OK
OK
OK
ESC
ESC
ESC
ESC
ESC
GRUNDFOS
INFORMATION:
WWW.GRUNDFOS.COM
ENTER PASSWORD
01987
[ 1 ]
AIR FLOW
X
m³/hr
GENERATING TIME
X
hrs
SERVICE MENU 1
X
AMPS
X
VOLTS
VOLTAGE ALARM
ALARM TIMER
X
sec
AIR FLOW
m³/hr
TANK HEIGHT
X
mm
TANK LEVEL
X %
TANK ALARM
PROGRAM NUMBER
X-XXXXXXXCCFM
Commissioning engineer code only
OK
ESC
LOW
HIGH
X
X
X
MIN
X
MAX
PRODUCTION
START
STOP
X %
X %
LOW
HIGH
0 %
0 %
Low and high limits normally 20-30 % above
and below voltage set point
Alarm delay timer normally 30-60 sec. "
AIR
FLOW
" alarm will be factory-set.
Working area height of product tank in mm
Enter required start and stop values in %
Enter required high and low alarm values in %
Main menu
SYSTEM OK
GENERATING
TANK LEVEL
X %
Service menu 1