Safety warning - electrical hazards

Before carrying out any form of inspection, maintenance or repair 
work on the system, operators must carry out tests to ensure that 
the plant has been satisfactorily isolated.

Safety warning - hydrogen gas

The electrolytic process of converting brine into sodium 
hypochlorite generates hydrogen gas which is vented to a safe 
external location through the degassing assembly via 
dual-contained pipework. The equipment should be regularly 
checked to ensure that no gas leakages occur.

There should be natural ventilation at a high and a low level in the 
room where the electrochlorinator is installed. A sign prohibiting 
smoking and naked flames should be displayed within the room 
and at the point of discharge to the exterior.
If required, a hydrogen detector can be fitted within the plant 
room to stop the Selcoperm system in the unlikely event of a 
build-up of hydrogen gas. This will also prevent the situation of an 
operator working in a potentially explosive environment.

Safety warning - hydrochloric acid

Hydrochloric acid is used to remove deposits from the electrodes 
(acid cleaning).

• If splashed onto skin, wash off with fresh water. Remove all 

affected clothing.

• If the eyes are affected, rinse them immediately using an 

approved eye shower or fresh running water for at least 15 
minutes, keeping the eyelid open and rotating the eye. Seek 
medical treatment immediately.

• If swallowed, do not induce vomiting. Keep the patient warm 

and quiet and seek immediate medical help. If the patient 
stops breathing, apply rescue breaths and cardiopulmonary 
resuscitation as necessary, until medical help arrives.

Rinse out all residual sodium hypochlorite from the system before 
filling with acid. Make sure the system is flushed well with water 
before restarting it.

Safety warning - brine

Salt is safe to handle, but eyes should be rinsed with fresh 
running water if subjected to brine splashes.

Personal protective equipment

Due to the range of hazardous chemicals any information 
provided in this section is only general. It is the duty of the 
operator to ensure that he has obtained information on all safety 
precautions relevant to the type of task he is undertaking, and to 
ensure that they are adhered to. Grundfos recommends to follow 
good practice when handling chemicals, and to use personal 
protective equipment such as ventilated, enclosed goggles, face 
shields, chemical aprons, boots and gloves. An eye shower may 
also be advisable.

2. Product description

2.1 Components

2.1.1 Selcoperm electrochlorinator

The electrochlorinater includes:
• A water softener to facilitate a water supply of the correct 

specification to the brine tank for providing the brine solution, 
and also to the electrolyser cell for dilution of the brine solution 
to the correct specific gravity (SG). The softener is water 
powered.

• A brine pump to dose the brine solution into the softened water 

line to the electrolyser cell.

• An electrolyser cell to convert the brine solution and softened 

water into a sodium hypochlorite solution of up to 0.65 %.

• A control panel to facilitate the low voltage/high current DC 

supply used in electrolysis.

• Operating elements monitoring and controlling the generation 

of sodium hypochlorite.

• An electrical fan system to dilute the hydrogen gas generated, 

and to force the ventilation of the gas to a safe external 
discharge point.

2.1.2 External components

The external components include:
• A brine tank providing a saturated brine solution. 

The saturated brine is mixed with soft water for electrolysis, 
and used for regeneration of the water softener.

• A product tank designed to store the sodium hypochlorite 

solution. This tank provides the buffer storage facility from 
which dosing can take place.

Warning
Danger of explosion!
When checking the equipment for leakages only use 
hydrogen detectors!
Never use a match or any type of flame!

Warning
Wear the stipulated personal protective equipment 
(protective clothing, goggles, respirator etc.) when 
handling chemicals.
Observe the chemical manufacturer's safety data 
sheets (MSDS) and safety instructions of the used 
chemicals.

Warning
If acid is mixed with sodium hypochlorite solution, 
highly hazardous chlorine gas is released.
Keep acid away from the sodium hypochlorite 
solution and the tank.
Display a warning notice locally.

Summary of Contents for Selcoperm SES 125-2000

Page 1: ...elcoperm SES 125 2000 Electrochlorinator Valid for SES 125 250 500 1000 built from week 37 2015 Valid for SES 2000 built from week 20 2014 Installation and operating instructions GRUNDFOS INSTRUCTIONS...

Page 2: ...em via a display with control and display elements 1 General safety instructions 2 1 1 Purpose of this document 2 1 2 Symbols used in this document 2 1 3 Users target groups 2 1 4 Obligations of the o...

Page 3: ...guaranteed for a period of two calendar years from installation and commissioning provided optimum operating conditions are as detailed in this manual The maximum period for full guarantee is 36 month...

Page 4: ...al It is the duty of the operator to ensure that he has obtained information on all safety precautions relevant to the type of task he is undertaking and to ensure that they are adhered to Grundfos re...

Page 5: ...ood switch F Soft water sample valve 7 Non return valve 19 Air dilution fan G Electrolyte sample valve 8 Water flow adjustment valve 20 Flowmeter switch H Product sample valve 9 Degassing column level...

Page 6: ...ment valve 21 Floater valve G Electrolyte sample valve 9 Degassing column level sensor 22 Control panel H Product sample valve 10 Pressure reducing valve 23 Control lamp of mains supply I Product over...

Page 7: ...ank M When the product reaches the stop fill level 25b in the product tank M the process is stopped The process is restarted when the product level in the tank M falls below the start fill level The p...

Page 8: ...minal g h 125 110 250 220 500 450 1000 900 2000 1800 Connection I imperial M metric Supply voltage frequency H 110 120 V 50 60 Hz G 220 240 V 50 60 Hz K 380 415 V 50 60 Hz Software language GB English...

Page 9: ...2 Dimensional drawing Fig 5 Dimensional drawing Type 125 250 500 1000 2000 Gross weight kg 299 309 319 334 349 Net weight kg 160 170 180 195 210 TM04 1594 3011 712 457 104 300 1570 1112 215 170 245 3...

Page 10: ...to 40 Permissible mains water operating temperature C 10 to 20 Transport and storage temperature drained and not connected C 5 to 50 Max altitude above sea level m 2000 System frame PP Chamber covers...

Page 11: ...k and collecting tray X30 7 X30 7 GND BN 24 VDC WH Signal GN Tray flood switch of product tank Product tank level sensor Single phase Three phase Mains power supply To customer telemetry Mains power s...

Page 12: ...ray No liquid in collecting tray Remote stop signal System stopped System running Emergency stop signal System stopped System running Data 125 125 250 500 1000 2000 single phase single phase three pha...

Page 13: ...ng Horizontal ventilation pipework has to be installed with a constant upwards incline towards a safe discharge point min 2000 min 700 min 150 1 Duty standby dosing pumps 5 Pressure level sensor 2 Pro...

Page 14: ...017 3 3 3 1 1 2 1 Soft water inlet 20 mm 2 Minimum gravel level 3 Brine outlets 20 mm Note Requirements and capacities of brine tank see section 3 6 Brine tank capacities TM04 1504 3011 6 5 4 3 2 2 1...

Page 15: ...VC pipework to the PE pipework Make sure that the product line from the electrolyser to the product tank is installed horizontally or downwards See fig 8 The table below shows the connection sizes for...

Page 16: ...lues Press ESC to exit the edit mode Once all values are set press ESC to exit service menu 1 and return to main display screen in main menu Warning Before making any electrical connections switch off...

Page 17: ...SC ESC ESC GRUNDFOS INFORMATION WWW GRUNDFOS COM ENTER PASSWORD 01987 1 AIR FLOW X m hr GENERATING TIME X hrs SERVICE MENU 1 X AMPS X VOLTS VOLTAGE ALARM ALARM TIMER X sec AIR FLOW m hr TANK HEIGHT X...

Page 18: ...d turn the screw clockwise until pin 2 is positioned in regeneration start range 4 for regenerating the right side of the softener During regeneration pin 2 moves clockwise Wait until pin 2 has left t...

Page 19: ...th isolating valve 16a For further advice please contact Grundfos 6 5 Checks during operation 6 5 1 Checking the water hardness A properly functioning water softener 4 is crucial for the efficiency an...

Page 20: ...ing time The alarm timer must be reset after completion of testing After the triggering of each alarm the electrochlorinator will need to be reset at control 28 6 8 1 Internal tray flood alarm The int...

Page 21: ...Safety installations which have been disabled during maintenance must be enabled again immediately after maintenance Warning Danger of personal injury from chlorine gas Sodium hypochlorite solution te...

Page 22: ...leaning If necessary clean all system surfaces with a moist and clean cloth 7 8 Acid cleaning 1 Switch off power supply at switch 29 and isolate system from the mains voltage 2 Connect hose to product...

Page 23: ...erature of electrolyser cell 1 to high CELL TEMP Mains water temperature to high Check and rectify High ambient temperature Ambient temperature must not exceed 40 C Faulty temperature sensor Replace t...

Page 24: ...or 98056760 Electrolyser cell SES 2000 14 98058479 Brine valve water softener 3 97721401 Brine pump SES 125 250 500 15 98058478 Brine injection valve 97722252 Brine pump SES 1000 2000 17 98056894 Inte...

Page 25: ...ller language Russian 2 95727184 Temperature sensor 3 98710813 Electrolyser power supply SES 125 98710815 Electrolyser power supply SES 250 98710816 Electrolyser power supply SES 500 98710817 Electrol...

Page 26: ...until spring 2009 TM04 1506 3311 Pos Product No Description 1 98056828 Side entry valve 2 95727187 3 4 lateral filter TM04 1595 3311 Pos Product No Description 1 98056894 Tray flood switch 2 95721859...

Page 27: ...Grundfos company or service workshop 11 Photos Fig 20 Correct installation of Venturi tee Fig 21 Typical installation Warning Before dismantling the system must be completely flushed with water in or...

Page 28: ...English GB 28 Fig 22 Installation pipework Fig 23 Safe ventilation point Subject to alterations TM04 1514 1210 TM04 1515 1210...

Page 29: ...niejsza dotyczy jest zgodny z nast puj cymi dyrektywami Rady w sprawie zbli enia przepis w prawnych pa stw cz onkowskich PT Declara o de conformidade UE A Grundfos declara sob sua nica responsabilidad...

Page 30: ...Declaration of conformity EAC 30 Declaration of conformity EAC 2 Selcoperm SES SEP 004 2011 010 2011 020 2011 TC RU C DK 30 01060 05 11 2019 153032 1 1 2016 143581 188...

Page 31: ...an GRUNDFOS Pumps K K 1 2 3 Shin Miyakoda Kita ku Hamamatsu 431 2103 Japan Phone 81 53 428 4760 Telefax 81 53 428 5005 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam...

Page 32: ...3971 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding...

Reviews: