background image

Eng

lish (US)

8

7. Installation

The separate nameplate supplied with the pump should be 
affixed at the installation site.
All safety regulations must be observed at the installation site, for 
instance the use of blowers for fresh air supply to the pit.

7.1 Cable protection

If the pump is not going to be installed immediately, the open end 
of the power supply cable or sensor cables must be protected 
from moisture which could otherwise penetrate the motor 
windings. This should be done as soon as the pump is delivered.
Protection can be carried out by fitting a cable cap or by wrapping 
the open end of the cable in plastic and taping over the plastic 
with strong waterproof tape.
If the pump system is configured for side discharge, locate the 
pump and column pipe cover so that the cable is 180 ° away from 
the discharge.

7.2 Installation procedure

The pump is installed in the stationary column pipe.
The pump operates completely submerged in the discharge flow 
and does not require any additional protection.
In addition to the pump, the following items are required:
• Column pipe with bottom locating plate, called seat ring, with 

integrated anti-rotation bracket on which the pump stands.

• Cable suspension system for securing the cable and 

regulating the height of the level sensors.

• The seat ring can be supplied with the pump as an installation 

accessory. Please contact Grundfos for details.

Take particular care when installing the KPL or KWM pumps, as 
the procedure is not similar to that of other submersible pumps. 
Make sure that the pump is aligned with the anti-rotation brackets 
and in such a way that pump rotation is prevented when the 
impeller is running.
The installation should be carried out by qualified personnel 
experienced in the installation of this type of pump.
The pump must be installed in compliance with this manual.
For installation dimensional requirements and pump dimensional 
data, see section 

15. Dimensions

 on page 18.

1. Measure the column pipe diameter (

D)

 and find the 

minimum height of the dimension (C) in the table below. 
Compare the dimension (C) with the actual measurement. 
The measured values must not be lower that the value in the 
table.The anchor bolts should be installed prior to concrete 
pouring as part of the construction works. If this is not done, 
then mark out and install the anchor bolts during the 
installation of the column pipe.

2. Installing the column pipe:

– Slowly lower the column pipe into the pit using overhead 

lifting equipment.

– Make sure that the column pipe is vertical and rests securely 

on the concrete.

– Tighten the anchor bolt nuts to ensure that the column pipe 

cannot move.

Fig. 8

Position of anchor bolt

3. Installing the pump:

– Make sure that the sealing O-ring is clean and located in the 

groove on the bottom of the pump housing. The O-ring seals 
between the pump housing and seat ring, preventing 
backflow.

– Slowly lower the pump into the column pipe using the 

overhead lifting equipment, if necessary. If lack of lifting 
height above column pipe, use an intermediate lifting ring, 
see fig 9. Carefully guide the pump into position at the 
bottom of the column pipe so that the pump does not tilt in 
any way on the stop vanes at the bottom of the column. Lift 
the pump approximately 1 in. (26 mm) and turn it counter-
clockwise until the anti-rotation brackets touch the nearest 
adjacent stop vanes.

– The pump is secured by its own weight and the anti-rotation 

brackets. No additional fixing is required.

4. Cable suspension system in the column pipe:

– It is important to fix the cables properly and according to 

these instructions in order to avoid damage to the cables 
during operation.

– Clamp wire rope and all cables together at distances of 

20 in. (508 mm) between the clamps adapted to weight of 
the cable. See fig. 9, cable clamps distance. Fasten the wire 
rope onto the eye at the top of the column pipe. Adjust the 
turnbuckle between the wire rope and the eye of the beam. 
Make sure that there is no slack in the cable suspension 
and that the cable is fastened and unable to swing.

– Lead the cables through the cable bushing of the column 

pipe top cover.

– Run the cables to the external terminal box. Make sure that 

the cable bushing is fitted correctly and prevents water 
leakage.

5. Fit the column pipe top cover on the upper part of the column 

pipe using a waterproof gasket, and tighten the bolts. 
Make sure that the cover prevents water leakage.

Warning
Before starting the installation, switch off the 
power supply and lock the mains switch in
the 0/Off position.
Any external voltage connected to the pump 
must be switched off before working on the 
pump.

Note

Note

Prior to installation, check the oil level in the oil 
chamber. See section 13.2.1 Oil level and oil 
condition.

T

M

05

 53

07

 36

1

2

Warning
Do not put your hands or any tool into the pump 
suction or discharge port after the pump has 
been connected to the power supply, unless the 
mains switch has been locked in the 0/Off 
position. 

Summary of Contents for KPL

Page 1: ...GRUNDFOS INSTRUCTIONS KPL KWM 15 to 1060 Hp Installation and operating instructions...

Page 2: ...o instructed GRUNDFOS WILL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES LOSSES OR EXPENSES ARISING FROM INSTALLATION USE OR ANY OTHER CAUSES THERE ARE NO EXPRESS OR IMPLIED WARRANTIES INC...

Page 3: ...the following flood and stormwater control drainage irrigation of large quantities of water raw water intake transfer of liquids in large scale municipal sewage treatment plants circulation of large...

Page 4: ...eplate supplied with the pump should be affixed at the installation site Fig 3 Nameplate Note Note When pumping liquids with a density and or a kinematic viscosity higher than the values stated above...

Page 5: ...power Hp 4 6 8 10 12 14 16 18 Number of poles 4 pole 6 pole 8 pole 10 pole 12 pole 14 pole 16 pole 18 pole T Number of phases Three phase motor 50 60 Frequency 50 Hz 60 Hz 9 11 13 15 17 19 21 Hydraul...

Page 6: ...irection from its normal position BS EN 809 1998 A1 2009 Fig 5 Single wire lift Fig 6 Double wire lift base support Fig 7 Double wire lift Warning Pump installation in pits must be carried out by spec...

Page 7: ...ry The pump should be periodically cleaned and sprayed with corrosion inhibiting oil The pump should always be stored under cover in a protected area not exposed to direct sunlight If the pump is stor...

Page 8: ...n pipe 2 Installing the column pipe Slowly lower the column pipe into the pit using overhead lifting equipment Make sure that the column pipe is vertical and rests securely on the concrete Tighten the...

Page 9: ...h only The cable suspension system may be adapted to the specific pump model Fig 9 Securing the cable to the lifting wire TM05 5940 4212 D Turnbuckle Sensor cable Power cable Intermediate lifting ring...

Page 10: ...o connect all three stator thermal sensors if bearing sensors are also connected Fig 11 Switches and sensors of KPL Fig 12 Switches and sensors of KWM TM03 9460 4007 Warning The ground earth lead is g...

Page 11: ...ion 11 Electrical connection They must also be connected to the safety circuit of the separate pump controller Technical data of moisture switches Two conductors operating voltage of switch 12 250 VAC...

Page 12: ...or IO 113 Publication no 98097396 One pump can be connected to an IO 113 Together with the sensors IO 113 forms a galvanic separation between the motor voltage in the pump and the controller connected...

Page 13: ...s ought to be fulfilled Consequences should be considered Requirements The thermal protection of the motor must be connected Peak voltage and dU dt must be in accordance with the table below The value...

Page 14: ...earth lead is at least two inches longer than the other leads after connection This is to ensure that if the cable is accidentally pulled out the ground earth lead connection will be the last to be d...

Page 15: ...er Replace worn parts if they impair function Check the clearance between the propeller impeller and the wear ring It must not exceed 0 078 in 20 mm Pumped liquid in oil chamber Warning If there has b...

Page 16: ...the propeller blade and the wear ring exceeds 0 078 in 20 mm the wear ring must be replaced 1 Remove the screws and lift the pump off the suction casing 2 Replace the wear ring 3 Assemble the pump in...

Page 17: ...ontact an authorized electrician d The phase currents are unbalanced or too high Contact an authorized electrician e The insulation between the phases and between phases and ground earth in the stator...

Page 18: ...English US 18 15 Dimensions 15 1 KPL dimensional sketch Fig 16 Dimensional sketch KPL TM05 5941 4212...

Page 19: ...L 7495 3400 118 2998 KPL 40 120 12 T 60 L 5754 2610 113 2871 KPL 40 175 12 T 60 L 5930 2690 113 2871 KPL 40 215 12 T 60 L 7187 3260 118 2998 KPL 48 215 14 T 60 L 9303 4220 132 3353 52 57 1336 46 85 11...

Page 20: ...English US 20 15 2 KWM dimensional sketch Fig 17 Dimensional sketch KWM TM05 8751 2613 I D1 H L D2 D3...

Page 21: ...38 97 990 35 82 910 37 79 950 KWM 40 300 8 T 60 H 6834 3100 110 04 2795 KWM 40 335 8 T 60 H 7407 3360 116 94 2970 KWM 40 215 10 T 60 M 7429 3370 121 85 3095 52 75 1340 25 60 650 38 97 990 35 82 910 3...

Page 22: ...57 1000 1450 24 610 12 305 43 55 1100 1400 55 67 1400 1700 28 712 14 356 51 69 1300 1750 65 83 1650 2100 32 813 16 407 55 83 1400 2100 71 98 1800 2500 36 915 18 458 59 100 1500 2550 77 118 1950 3000...

Page 23: ...Fig 20 Installation dimensions KPL pump ACC installed Fig 21 Installation dimensions KPL pump Fig 22 Installation dimensions KPL pump TM05 9452 3813 TM05 9453 3813 D C S M W L D C S M W L TM05 9454 38...

Page 24: ...55 1100 1400 55 67 1400 1700 28 712 14 356 15 7 400 51 69 1300 1750 65 83 1650 2100 32H 16 407 16 7 425 55 83 1400 2100 71 98 1800 2500 32M 16 483 17 3 440 55 83 1400 2100 71 98 1800 2500 36 915 18 45...

Page 25: ...KWM pump Fig 27 Installation dimension KWM pump Fig 28 Installation dimension KWM pump Fig 29 Installation dimensions KWM pump TM05 9457 3813 TM05 9458 3813 D C I S M W L D C I S M W L TM05 9459 3813...

Page 26: ...roduct or parts of it must be disposed of in an environmentally sound way 1 Use the public or private waste collection service 2 If this is not possible contact the nearest Grundfos company or service...

Page 27: ...ine starting DOL three power cables Fig 4 Star delta starting Y D one power cable TM05 6180 4512 TM05 6181 4512 V1 W1 U1 M 3 PE Control cable L1 L2 L3 PE V1 W1 U1 PE M 3 V2 W2 U2 PE Control cable L1 L...

Page 28: ...COM WIO M M Symbol Description Symbol Description Thermal switch Pt100 sensor Moisture switch Earth lead Water in oil sensor T M WIO TM05 9585 4514 PE T1 T2 G1 A1 G2 A2 K1 K2 R1 R2 D1 D2 D3 D4 D5 D6...

Page 29: ...00 B S L B S H COM1 MS TP B P5 P4 MS TP B COM2 M M Symbol Description Thermal switch Moisture switch Pt100 sensor Earth lead Water in oil sensor M T WIO PE T1 T2 G1 A1 G2 A2 K1 K2 R1 R2 D1 D2 D3 D4 D5...

Page 30: ...30...

Page 31: ...ace Olathe KS 66061 Phone 1 913 227 3400 Fax 1 913 227 3500 www grundfos us Canada GRUNDFOS Canada 2941 Brighton Road Oakville Ontario L6H 6C9 Canada Phone 1 905 829 9533 Telefax 1 905 829 9512 www gr...

Page 32: ...ECM 1137521 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos...

Reviews: