background image

Eng

lish (US)

12

8.4 WIO (water-in-oil) sensor

The WIO sensor measures the water content in the oil chamber 
and converts the value into an analog current signal. The two 
sensor leads are for power supply and for carrying the signal to 
the measuring device or controller. The sensor measures the 
water content from 0 to 20 %. It also sends a signal if the water 
content is outside the normal range (warning), or if oil level is low 
(alarm). The sensor is fitted in a stainless steel tube for 
mechanical protection.
The WIO sensor can be used together with Grundfos IO 113 or 
SM 113, but it can also be used together with other controllers 
with 4-20 mA inputs.
Together with IO 113, the WIO sensor filters the signal and 
provides an easy readout of the actual value. Furthermore, it is 
possible to set a user-defined warning limit and calibrate the 
IO 113 and the sensor to the motor oil.

The WIO sensor works in the following way:

Sensor signals

Technical data

8.5 Pump vibration sensor (PVS 3)

The PVS 3 sensor monitors the vibration level of the pump in 
order to protect the pump and the pipe system against damage. 
A change in the vibration level is an indication of an abnormal 
situation. The reason for this can be a clogged impeller, worn 
bearings, a closed discharge valve etc., indicating that a service 
inspection should be carried out before the pump or the pipe 
system is damaged.

9. Monitoring and control of pump

9.1 IO 113

IO 113 forms the interface between a Grundfos stormwater or 
wastewater pump with analog and digital sensors and the pump 
controller. The most important sensor data are indicated on the 
front panel. See also the installation and operating instructions for 
IO 113 (Publication no. 98097396).
One pump can be connected to an IO 113.
Together with the sensors, IO 113 forms a galvanic separation 
between the motor voltage in the pump and the controller 
connected.
IO 113 with SM 113 enables the following functions:
• protecting the pump against overtemperature
• monitoring the sensors for analog measurement of:

– motor temperature
– pump vibrations
– leakages (WIO)
– stator insulation resistance
– bearing temperature
– digital measurement of moisture in motor

• stopping the pump in case of alarm
• remotely monitoring the pump via RS485 communication 

(Modbus or GENIbus).

Measurement of insulation resistance

IO 113 measures the insulation resistance between a stator 
winding and ground (earth):
• Resistance above 10 M

 = ok

• Resistance between 10 M

 and 1 M

 = warning

• Resistance below 1 M

 = alarm.

9.2 SM 113

SM 113 is used for collecting and transferring sensor data.
SM 113 works together with the IO 113 through power line 
communication using the Grundfos GENIbus protocol.
SM 113 module can be placed either inside the pump terminal 
box (allowing fewer sensor leads out of the pump) or in the 
control cabinet next to the pump installation. For electrical 
connection see fig. 5-8. SM 113 collects data from the following 
devices:
• 3 current sensors, 4-20 mA
• 3 Pt 100 thermal sensors 
• 1 PTC thermal sensor 
• 1 digital input.

Caution

Lack of oil may cause overheating and damage of 
the mechanical shaft seals. The WIO sensor in 
the oil chamber will trip the alarm if the oil quality 
is poor or there is not enough oil in the oil 
chamber.

Note

Note

The sensor signal is only valid when oil and 
water is mixed (when the pump is running).

4-20 mA =

0-20 % water in oil
Accuracy better than 2 %

22 mA

=

Warning:
Water content above 20 % 

3.5 mA

=

Alarm:
Air in the oil chamber

Input voltage:

12-24 VDC 

Output current:

3.4 - 22 mA

Power input:

0.6 W

Ambient temperature:

32 to 158 °F (0 to 70 °C)

Summary of Contents for KPL

Page 1: ...GRUNDFOS INSTRUCTIONS KPL KWM 15 to 1060 Hp Installation and operating instructions...

Page 2: ...o instructed GRUNDFOS WILL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES LOSSES OR EXPENSES ARISING FROM INSTALLATION USE OR ANY OTHER CAUSES THERE ARE NO EXPRESS OR IMPLIED WARRANTIES INC...

Page 3: ...the following flood and stormwater control drainage irrigation of large quantities of water raw water intake transfer of liquids in large scale municipal sewage treatment plants circulation of large...

Page 4: ...eplate supplied with the pump should be affixed at the installation site Fig 3 Nameplate Note Note When pumping liquids with a density and or a kinematic viscosity higher than the values stated above...

Page 5: ...power Hp 4 6 8 10 12 14 16 18 Number of poles 4 pole 6 pole 8 pole 10 pole 12 pole 14 pole 16 pole 18 pole T Number of phases Three phase motor 50 60 Frequency 50 Hz 60 Hz 9 11 13 15 17 19 21 Hydraul...

Page 6: ...irection from its normal position BS EN 809 1998 A1 2009 Fig 5 Single wire lift Fig 6 Double wire lift base support Fig 7 Double wire lift Warning Pump installation in pits must be carried out by spec...

Page 7: ...ry The pump should be periodically cleaned and sprayed with corrosion inhibiting oil The pump should always be stored under cover in a protected area not exposed to direct sunlight If the pump is stor...

Page 8: ...n pipe 2 Installing the column pipe Slowly lower the column pipe into the pit using overhead lifting equipment Make sure that the column pipe is vertical and rests securely on the concrete Tighten the...

Page 9: ...h only The cable suspension system may be adapted to the specific pump model Fig 9 Securing the cable to the lifting wire TM05 5940 4212 D Turnbuckle Sensor cable Power cable Intermediate lifting ring...

Page 10: ...o connect all three stator thermal sensors if bearing sensors are also connected Fig 11 Switches and sensors of KPL Fig 12 Switches and sensors of KWM TM03 9460 4007 Warning The ground earth lead is g...

Page 11: ...ion 11 Electrical connection They must also be connected to the safety circuit of the separate pump controller Technical data of moisture switches Two conductors operating voltage of switch 12 250 VAC...

Page 12: ...or IO 113 Publication no 98097396 One pump can be connected to an IO 113 Together with the sensors IO 113 forms a galvanic separation between the motor voltage in the pump and the controller connected...

Page 13: ...s ought to be fulfilled Consequences should be considered Requirements The thermal protection of the motor must be connected Peak voltage and dU dt must be in accordance with the table below The value...

Page 14: ...earth lead is at least two inches longer than the other leads after connection This is to ensure that if the cable is accidentally pulled out the ground earth lead connection will be the last to be d...

Page 15: ...er Replace worn parts if they impair function Check the clearance between the propeller impeller and the wear ring It must not exceed 0 078 in 20 mm Pumped liquid in oil chamber Warning If there has b...

Page 16: ...the propeller blade and the wear ring exceeds 0 078 in 20 mm the wear ring must be replaced 1 Remove the screws and lift the pump off the suction casing 2 Replace the wear ring 3 Assemble the pump in...

Page 17: ...ontact an authorized electrician d The phase currents are unbalanced or too high Contact an authorized electrician e The insulation between the phases and between phases and ground earth in the stator...

Page 18: ...English US 18 15 Dimensions 15 1 KPL dimensional sketch Fig 16 Dimensional sketch KPL TM05 5941 4212...

Page 19: ...L 7495 3400 118 2998 KPL 40 120 12 T 60 L 5754 2610 113 2871 KPL 40 175 12 T 60 L 5930 2690 113 2871 KPL 40 215 12 T 60 L 7187 3260 118 2998 KPL 48 215 14 T 60 L 9303 4220 132 3353 52 57 1336 46 85 11...

Page 20: ...English US 20 15 2 KWM dimensional sketch Fig 17 Dimensional sketch KWM TM05 8751 2613 I D1 H L D2 D3...

Page 21: ...38 97 990 35 82 910 37 79 950 KWM 40 300 8 T 60 H 6834 3100 110 04 2795 KWM 40 335 8 T 60 H 7407 3360 116 94 2970 KWM 40 215 10 T 60 M 7429 3370 121 85 3095 52 75 1340 25 60 650 38 97 990 35 82 910 3...

Page 22: ...57 1000 1450 24 610 12 305 43 55 1100 1400 55 67 1400 1700 28 712 14 356 51 69 1300 1750 65 83 1650 2100 32 813 16 407 55 83 1400 2100 71 98 1800 2500 36 915 18 458 59 100 1500 2550 77 118 1950 3000...

Page 23: ...Fig 20 Installation dimensions KPL pump ACC installed Fig 21 Installation dimensions KPL pump Fig 22 Installation dimensions KPL pump TM05 9452 3813 TM05 9453 3813 D C S M W L D C S M W L TM05 9454 38...

Page 24: ...55 1100 1400 55 67 1400 1700 28 712 14 356 15 7 400 51 69 1300 1750 65 83 1650 2100 32H 16 407 16 7 425 55 83 1400 2100 71 98 1800 2500 32M 16 483 17 3 440 55 83 1400 2100 71 98 1800 2500 36 915 18 45...

Page 25: ...KWM pump Fig 27 Installation dimension KWM pump Fig 28 Installation dimension KWM pump Fig 29 Installation dimensions KWM pump TM05 9457 3813 TM05 9458 3813 D C I S M W L D C I S M W L TM05 9459 3813...

Page 26: ...roduct or parts of it must be disposed of in an environmentally sound way 1 Use the public or private waste collection service 2 If this is not possible contact the nearest Grundfos company or service...

Page 27: ...ine starting DOL three power cables Fig 4 Star delta starting Y D one power cable TM05 6180 4512 TM05 6181 4512 V1 W1 U1 M 3 PE Control cable L1 L2 L3 PE V1 W1 U1 PE M 3 V2 W2 U2 PE Control cable L1 L...

Page 28: ...COM WIO M M Symbol Description Symbol Description Thermal switch Pt100 sensor Moisture switch Earth lead Water in oil sensor T M WIO TM05 9585 4514 PE T1 T2 G1 A1 G2 A2 K1 K2 R1 R2 D1 D2 D3 D4 D5 D6...

Page 29: ...00 B S L B S H COM1 MS TP B P5 P4 MS TP B COM2 M M Symbol Description Thermal switch Moisture switch Pt100 sensor Earth lead Water in oil sensor M T WIO PE T1 T2 G1 A1 G2 A2 K1 K2 R1 R2 D1 D2 D3 D4 D5...

Page 30: ...30...

Page 31: ...ace Olathe KS 66061 Phone 1 913 227 3400 Fax 1 913 227 3500 www grundfos us Canada GRUNDFOS Canada 2941 Brighton Road Oakville Ontario L6H 6C9 Canada Phone 1 905 829 9533 Telefax 1 905 829 9512 www gr...

Page 32: ...ECM 1137521 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos...

Reviews: