background image

13

English (US)

9.3 Pump controllers

The KPL, KWM pumps can be connected to a separate Grundfos 
pump controller for level control, which is available as an 
accessory:
• type LC for one-pump installations
• type LCD for two-pump installations
• Grundfos Dedicated Controls for one to six pumps.
Depending on the application, different types of level control 
equipment can be used:

The LC controller

 is fitted with two or three level switches. 

Two for start and stop of the pump. The third level switch, which 
is optional, is for high-level alarm.

The LCD controller

 is fitted with three or four level switches.

One for common stop and two for start of the pumps. The fourth 
level switch, which is optional, is for high-level alarm.

Grundfos Dedicated Controls

 are control systems designed for 

installation in either commercial buildings or network pumping 
stations with up to six pumps. Advanced control and data 
communication is also possible with Grundfos Dedicated Controls 
systems.
The Grundfos Dedicated Controls system consists of the 
following components:
• CU 361 control unit
• IO 351B module (general I/O module)
• IO 113 protection module (optional).
Grundfos Dedicated Controls systems starts/stop pumps by 
means of the following devices:
• float switches
• analog pressure sensors
• ultrasonic sensors.
Furthermore, it is possible to control the water level by combining 
float switches with an analog pressure sensor. Two additional 
safety float switches can be installed in the Dedicated Controls 
system for high-level and dry-running alarm.

10. Variable frequency drive operation

In principle, all three-phase motors can be connected to a 
variable frequency drive.
However, variable frequency drive operation will often expose the 
motor insulation system to a heavier load and cause the motor to 
be more noisy than usual due to eddy currents caused by voltage 
peaks.
For variable frequency drive operation, please observe the 
following:
• Requirements must be fulfilled.
• Recommendations ought to be fulfilled.
• Consequences should be considered.

Requirements

• The thermal protection of the motor must be connected.
• Peak voltage and dU/dt must be in accordance with the table 

below. The values stated are maximum values supplied to the 
motor terminals. The cable influence has not been taken into 
account. See the variable frequency drive data sheet 
regarding the actual values and the cable influence on the 
peak voltage and dU/dt.

• Set the variable frequency drive U/f ratio according to the 

motor data.

• Local regulations/standards must be fulfilled.

Recommendations

Before installing a variable frequency drive, calculate the lowest 
allowable frequency in the installation in order to avoid zero flow.
• Do not reduce the motor speed to less than 25 % of rated 

speed. 

• Keep the flow velocity above 3.3 ft/sec; recommended 

minimum velocity ~3 ft./sec.

• If the pumping liquid is available, then the pump should be run 

at rated speed at least once a day in order to prevent 
sedimentation in the piping system.

• Do not exceed the frequency indicated on the nameplate as 

this may cause motor overload.

• Keep the motor cable as short as possible. The peak voltage 

will increase with the length of the motor cable. See data sheet 
for the variable frequency drive used.

• Use input and output filters on the variable frequency drive. 

See data sheet for the variable frequency drive used.

• Use a screened motor cable if there is a risk that electrical 

noise may disturb other electrical equipment. See data sheet 
for the variable frequency drive used.

Consequences

When operating the pump via a variable frequency drive, please 
be aware of these possible consequences:
• The locked-rotor torque will be lower; how much lower will 

depend on the variable frequency drive type. See the 
Installation and Operating Instructions for the variable 
frequency drive used, for information on the locked-rotor 
torque available.

• The acoustic noise level may increase. See the Installation 

and Operating Instructions for the variable frequency drive 
used, for advice as to how to reduce the acoustic noise.

Maximum repetitive peak 

voltage (400 V / 460 V)

[V]

Maximum dU/dt 

U

N

 (400 V - 460 V)

[V/

μ

 sec.]

850

2000

Summary of Contents for KPL

Page 1: ...GRUNDFOS INSTRUCTIONS KPL KWM 15 to 1060 Hp Installation and operating instructions...

Page 2: ...o instructed GRUNDFOS WILL NOT BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES LOSSES OR EXPENSES ARISING FROM INSTALLATION USE OR ANY OTHER CAUSES THERE ARE NO EXPRESS OR IMPLIED WARRANTIES INC...

Page 3: ...the following flood and stormwater control drainage irrigation of large quantities of water raw water intake transfer of liquids in large scale municipal sewage treatment plants circulation of large...

Page 4: ...eplate supplied with the pump should be affixed at the installation site Fig 3 Nameplate Note Note When pumping liquids with a density and or a kinematic viscosity higher than the values stated above...

Page 5: ...power Hp 4 6 8 10 12 14 16 18 Number of poles 4 pole 6 pole 8 pole 10 pole 12 pole 14 pole 16 pole 18 pole T Number of phases Three phase motor 50 60 Frequency 50 Hz 60 Hz 9 11 13 15 17 19 21 Hydraul...

Page 6: ...irection from its normal position BS EN 809 1998 A1 2009 Fig 5 Single wire lift Fig 6 Double wire lift base support Fig 7 Double wire lift Warning Pump installation in pits must be carried out by spec...

Page 7: ...ry The pump should be periodically cleaned and sprayed with corrosion inhibiting oil The pump should always be stored under cover in a protected area not exposed to direct sunlight If the pump is stor...

Page 8: ...n pipe 2 Installing the column pipe Slowly lower the column pipe into the pit using overhead lifting equipment Make sure that the column pipe is vertical and rests securely on the concrete Tighten the...

Page 9: ...h only The cable suspension system may be adapted to the specific pump model Fig 9 Securing the cable to the lifting wire TM05 5940 4212 D Turnbuckle Sensor cable Power cable Intermediate lifting ring...

Page 10: ...o connect all three stator thermal sensors if bearing sensors are also connected Fig 11 Switches and sensors of KPL Fig 12 Switches and sensors of KWM TM03 9460 4007 Warning The ground earth lead is g...

Page 11: ...ion 11 Electrical connection They must also be connected to the safety circuit of the separate pump controller Technical data of moisture switches Two conductors operating voltage of switch 12 250 VAC...

Page 12: ...or IO 113 Publication no 98097396 One pump can be connected to an IO 113 Together with the sensors IO 113 forms a galvanic separation between the motor voltage in the pump and the controller connected...

Page 13: ...s ought to be fulfilled Consequences should be considered Requirements The thermal protection of the motor must be connected Peak voltage and dU dt must be in accordance with the table below The value...

Page 14: ...earth lead is at least two inches longer than the other leads after connection This is to ensure that if the cable is accidentally pulled out the ground earth lead connection will be the last to be d...

Page 15: ...er Replace worn parts if they impair function Check the clearance between the propeller impeller and the wear ring It must not exceed 0 078 in 20 mm Pumped liquid in oil chamber Warning If there has b...

Page 16: ...the propeller blade and the wear ring exceeds 0 078 in 20 mm the wear ring must be replaced 1 Remove the screws and lift the pump off the suction casing 2 Replace the wear ring 3 Assemble the pump in...

Page 17: ...ontact an authorized electrician d The phase currents are unbalanced or too high Contact an authorized electrician e The insulation between the phases and between phases and ground earth in the stator...

Page 18: ...English US 18 15 Dimensions 15 1 KPL dimensional sketch Fig 16 Dimensional sketch KPL TM05 5941 4212...

Page 19: ...L 7495 3400 118 2998 KPL 40 120 12 T 60 L 5754 2610 113 2871 KPL 40 175 12 T 60 L 5930 2690 113 2871 KPL 40 215 12 T 60 L 7187 3260 118 2998 KPL 48 215 14 T 60 L 9303 4220 132 3353 52 57 1336 46 85 11...

Page 20: ...English US 20 15 2 KWM dimensional sketch Fig 17 Dimensional sketch KWM TM05 8751 2613 I D1 H L D2 D3...

Page 21: ...38 97 990 35 82 910 37 79 950 KWM 40 300 8 T 60 H 6834 3100 110 04 2795 KWM 40 335 8 T 60 H 7407 3360 116 94 2970 KWM 40 215 10 T 60 M 7429 3370 121 85 3095 52 75 1340 25 60 650 38 97 990 35 82 910 3...

Page 22: ...57 1000 1450 24 610 12 305 43 55 1100 1400 55 67 1400 1700 28 712 14 356 51 69 1300 1750 65 83 1650 2100 32 813 16 407 55 83 1400 2100 71 98 1800 2500 36 915 18 458 59 100 1500 2550 77 118 1950 3000...

Page 23: ...Fig 20 Installation dimensions KPL pump ACC installed Fig 21 Installation dimensions KPL pump Fig 22 Installation dimensions KPL pump TM05 9452 3813 TM05 9453 3813 D C S M W L D C S M W L TM05 9454 38...

Page 24: ...55 1100 1400 55 67 1400 1700 28 712 14 356 15 7 400 51 69 1300 1750 65 83 1650 2100 32H 16 407 16 7 425 55 83 1400 2100 71 98 1800 2500 32M 16 483 17 3 440 55 83 1400 2100 71 98 1800 2500 36 915 18 45...

Page 25: ...KWM pump Fig 27 Installation dimension KWM pump Fig 28 Installation dimension KWM pump Fig 29 Installation dimensions KWM pump TM05 9457 3813 TM05 9458 3813 D C I S M W L D C I S M W L TM05 9459 3813...

Page 26: ...roduct or parts of it must be disposed of in an environmentally sound way 1 Use the public or private waste collection service 2 If this is not possible contact the nearest Grundfos company or service...

Page 27: ...ine starting DOL three power cables Fig 4 Star delta starting Y D one power cable TM05 6180 4512 TM05 6181 4512 V1 W1 U1 M 3 PE Control cable L1 L2 L3 PE V1 W1 U1 PE M 3 V2 W2 U2 PE Control cable L1 L...

Page 28: ...COM WIO M M Symbol Description Symbol Description Thermal switch Pt100 sensor Moisture switch Earth lead Water in oil sensor T M WIO TM05 9585 4514 PE T1 T2 G1 A1 G2 A2 K1 K2 R1 R2 D1 D2 D3 D4 D5 D6...

Page 29: ...00 B S L B S H COM1 MS TP B P5 P4 MS TP B COM2 M M Symbol Description Thermal switch Moisture switch Pt100 sensor Earth lead Water in oil sensor M T WIO PE T1 T2 G1 A1 G2 A2 K1 K2 R1 R2 D1 D2 D3 D4 D5...

Page 30: ...30...

Page 31: ...ace Olathe KS 66061 Phone 1 913 227 3400 Fax 1 913 227 3500 www grundfos us Canada GRUNDFOS Canada 2941 Brighton Road Oakville Ontario L6H 6C9 Canada Phone 1 905 829 9533 Telefax 1 905 829 9512 www gr...

Page 32: ...ECM 1137521 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos...

Reviews: