Eng
lish (US)
10
7.3 Lead colors
Fig. 10
Lead colors, example direct-online-starting (DOL) two
power cables
The use of 8 core and 11 core cables will be specified according
to sensor options. See pages 28-29.
For wiring diagrams, see Appendix on page 27:
Figure 1 shows direct-online-starting (DOL), one power cable.
Figure 2 shows direct-online-starting (DOL), two power cables.
Figure 3 shows direct-online-starting (DOL), three power cables.
Figure 4 shows star-delta starting (Y/D), one power cable.
8. Pump protection
KPL, KWM pumps are equipped with the following protective
switches and sensors. In the Factory Product Variant (FPV)
version, the sensors can be chosen individually.
(1)
Three Pt-100 sensors are mounted in the pump from factory,
but only one sensor is connected as standard. It is not
possible to connect all three stator thermal sensors, if bearing
sensors are also connected.
Fig. 11
Switches and sensors of KPL
Fig. 12
Switches and sensors of KWM
TM
03
94
60
40
07
Warning
The ground (earth) lead is green and marked
"PE".
Sensor
Type
Standard
[Qty]
FPV
[Qty]
Stator thermal protection
Bi-metal
3
3
Stator thermal protection
Pt-100
1
3
(1)
Terminal box moisture switch
Switch
1
1
Motor housing moisture switch
Switch
1
1
Bearing thermal protection
(lower)
Pt-100
1
1
Bearing thermal protection
(upper)
Pt-100
1
1
Water-in-oil sensor (WIO)
Analog
1
Vibration sensor PVS3
Analog
1
Primary power cable
Secondary power cable
Sensor cable
U1 (red)
W1 (black)
V1 (white)
Ground(earth)
(green)
V2 (white)
W2 (black)
U2 (red)
1 to 7 (10) (white)
Ground(earth)
(green)
Ground(earth)
(green)
TM
05
9
557
40
13
T
M
05
95
58
40
13
Thermal
sensor
Moisture
switch
Thermal switch/
sensor
Moisture
switch
Thermal
sensor
WIO
Vibration
sensor
Thermal
sensor
Moisture
switch
Thermal switch/
sensor
Moisture
switch
Thermal
sensor
WIO
Vibration
sensor