4.4 Installation example
The drawing shows an installation example.
The DME pump can be installed in many different
ways. The sketch below shows an example with side-
fitted control panel. The tank is a Grundfos chemical
tank with a Grundfos level control unit.
TM027065
4.5 Electrical connection
•
The electrical connection of the pump should be
carried out by qualified persons in accordance
with local regulations.
•
For electrical data of the pump, see section
Electrical data.
•
Do not lay signal cables, if any, together with
power cables.
Warning
Danger to life due to non-tripping of the
residual current device (RCD)!
If the pump is connected to an electric
installation where a residual current device
(RCD) is used as an additional protection,
this RCD must trip when earth fault
currents with DC content (pulsating DC)
and smooth DC earth fault currents occur.
This means that a RCD type B, sensitive
to universal current, must be used.
Related information
13
English (GB)