English (GB)
49
1.
Relay function (stroke / pre-empty / pulse
selection)
"1:OFF", "1:ON" or "1:1:1" appears in the display.
•
Use the "Up" and "Down" buttons to switch
between:
– "1:OFF": Relay function = stroke signal
("1/min" flashes in the display), and
– "1:ON": Relay function = pre-empty signal
(empty-signal symbol flashes in the display),
and
– "1:1:1": Relay function = pulse input
("n:1" flashes in the display).
•
Press the "Menu/Info" button (confirm the setting
and move on to the next menu item), or
•
press the "Start/Stop" button (confirm the setting
and close the service level).
2.
Relay output, NO/NC (stroke / pre-empty /
pulse)
"2:NO" or "2:NC" appears in the display
("1/min" and empty-signal symbol flash in the
display).
•
Use the "Up" and "Down" buttons to switch
between:
– "2:NO": Stroke/pre-empty signal/pulse input
relay = normally open contact, and
– "2:NC": Stroke/pre-empty signal/pulse input
relay = normally closed contact.
•
Press the "Menu/Info" button (confirm the setting
and move on to the next menu item), or
•
press the "Start/Stop" button (confirm the setting
and close the service level).
3.
Pre-empty signal, NO/NC input
"3:NO" or "3:NC" appears in the display
(empty-signal symbol flashes in the display).
•
Use the "Up" and "Down" buttons to switch
between:
– "3:NO": Pre-empty signal = normally open
contact, and
– "3:NC": Pre-empty signal = normally closed
contact.
•
Press the "Menu/Info" button (confirm the setting
and move on to the next menu item), or
•
press the "Start/Stop" button (confirm the setting
and close the service level).
4.
Empty signal, NO/NC input
"4:NO" or "4:NC" appears in the display
(empty-signal symbol lights up in the display).
•
Use the "Up" and "Down" buttons to switch
between:
– "4:NO": Empty signal = normally open contact,
and
– "4:NC": Empty signal = normally closed
contact.
•
Press the "Menu/Info" button (confirm the setting
and move on to the next menu item), or
•
press the "Start/Stop" button (confirm the setting
and close the service level).
5.
Error signal, NO/NC output
"5:NO" or "5:NC" appears in the display ("ERROR"
flashes in the display).
•
Use the "Up" and "Down" buttons to switch
between:
– "5:NO": Error signal relay = normally open
contact, and
– "5:NC": Error signal relay = normally closed
contact.
•
Press the "Menu/Info" button (confirm the setting
and move on to the next menu item), or
•
press the "Start/Stop" button (confirm the setting
and close the service level).
6.
Remote off, NO/NC input
"6:NO" or "6:NC" appears in the display
("Run" and "Stop" flash in the display).
•
Use the "Up" and "Down" buttons to switch
between:
– "6:NO": Remote off = normally open contact,
and
– "6:NC": Remote off = normally closed contact.
•
Press the "Menu/Info" button (confirm the setting
and move on to the next menu item), or
•
press the "Start/Stop" button (confirm the setting
and close the service level).
7.
Locking "run" on/off
The locking of the "Start/Stop" button to prevent
manual stopping of the pump can be enabled and
disabled.
The display indicates "7:ON" or "7:OFF"
(the "Run" symbol is displayed).
•
Use the "Up" and "Down" buttons to switch
between:
– "7:ON": Locking "run" on, and
– "7:OFF": Locking "run" off.
•
Press the "Menu/Info" button (confirm the setting
and move on to the next menu item), or
•
press the "Start/Stop" button (confirm the setting
and close the service level).
P: CAL on/off (only for Flow Monitor)
"CAL:ON" or "CAL:OFF" appears in the display
("CAL" appears).
•
Use the "Up" and "Down" buttons to switch
between:
– "CAL:ON": Calibration of the pressure sensor
for the Flow Monitor enabled, and
– "CAL:OFF": Calibration of the pressure sensor
for the Flow Monitor disabled.
St: e.g. "60" (only for Flow Monitor)
•
Use the "Up" and "Down" buttons to set the
"number of error strokes permitted when
starting". If the number of error strokes is
exceeded, the "Flow error" error message
appears.
Note
For calibration, see section
9.10.7 Calibrating the sensor after the
sensor has been replaced.