12
8.3 Installation altitude
Installation altitude is the height above sea level of
the installation site.
Motors installed up to 1000 m above sea level can
be loaded 100 %.
The motors can be installed up to 3500 m above sea
level.
Fig. 10
Motor output power in relation to altitude
In order to maintain the galvanic isolation and ensure
correct clearance according to EN 60664-1:2007,
you must adapt the supply voltage to the altitude:
Fig. 11
Supply voltage for three-phase motor in
relation to altitude
8.4 Humidity
Maximum humidity: 95 %.
If the humidity is constantly high and above 85 %,
open the drain holes in the drive-end flange. See
section
8.5 Motor cooling
To ensure cooling of motor and electronics, observe
the following:
•
Position the motor in such a way that adequate
cooling is ensured. See section
•
The temperature of the cooling air must not
exceed 50 °C.
•
Keep cooling fins and fan blades clean.
9. User interfaces
You can make the pump settings by means of the
following user interfaces:
Operating panels
•
Basic operating panel.
See section
Remote controls
•
Grundfos GO Remote.
See section
If the power supply to the pump is switched off, the
settings are stored.
Motors installed more than 1000 m above
sea level must not be fully loaded due to
the low density and consequent low
cooling effect of the air.
TM
0
5
5
243
3
717
TM
06
98
6
6
36
17
0
60
80
90
70
100
500 1000 1500 2000 2500 3000 3500
Altitude [m]
P2 [%]
500
2500
3500
1500
500
480
460
440
420
380
400
Y
X
Supply voltage [V]
Altitude [m]
WARNING
Hot surface
Death or serious personal injury
- Only touch the buttons on the display as
the product may be very hot.