Digital input, DI
Internal pull-up current greater than 10 mA at V
i
equal 0 VDC.
Internal pull-up to 5 VDC (currentless for V
i
greater
than 5 VDC).
Certain low logic level: V
i
less than 1.5 VDC.
Certain high logic level: V
i
greater than 3.0 VDC.
Hysteresis: No.
Screened cable: 0.5 - 1.5 mm
2
, 28-16 AWG.
Maximum cable length: 500 m.
Analog input, AI
Voltage signal ranges:
•
0.5 - 3.5 VDC, AL AU.
•
0-5 VDC, AU.
•
0-10 VDC, AU.
Voltage signal: R
i
greater than 100 k
Ω
at 25 °C.
Leak currents may occur at high operating
temperatures. Keep the source impedance low.
Current signal ranges:
•
0-20 mADC, AU.
•
4-20 mADC, AL AU.
Current signal: R
i
is equal to 292
Ω
.
Current overload protection: Yes. Change to voltage
signal.
Measurement tolerance: - 0/+ 3 % of full scale
(maximum-point coverage).
Screened cable: 0.5 - 1.5 mm
2
, 28-16 AWG.
Maximum cable length: 500 m excluding
potentiometer.
Potentiometer connected to +5 V, GND:
Use maximum 10 k
Ω
.
Maximum cable length: 100 m.
Power supplies
+5 V:
•
Output voltage: 5 VDC - 5 %/+ 5 %.
•
Maximum current: 50 mADC (sourcing only).
•
Overload protection: Yes.
+24 V:
•
Output voltage: 24 VDC - 5 %/+ 5 %.
•
Maximum current: 60 mADC (sourcing only).
•
Overload protection: Yes.
Relay
Potential-free changeover contacts.
Minimum contact load when in use: 5 VDC, 10 mA.
Screened cable: 0.5 - 2.5 mm
2
, 28-12 AWG.
Maximum cable length: 500 m.
Bus input
Grundfos GENIbus protocol, RS-485.
Screened 3-core cable: 0.5 - 1.5 mm
2
, 28-16 AWG.
Maximum cable length: 500 m.
24. Other technical data
EMC (electromagnetic compatibility)
Standard used: EN 61800-3.
The table below shows the emission category of the
motor.
C2 fulfils the requirements for residential areas. Note
that when connected to a public network, 11 kW
motors do not comply with the partial weighted
harmonic distortion (PWHD) requirements of EN
61000-3-12. If required by the distribution network
operator, compliance can be obtained in the
following way:
The impedance of the mains cables between the
motor and the point of common coupling (PCC) must
be equivalent to the impedance of a 50 m cable with
a cross-section of 0.5 mm.
C3 fulfils the requirements for industrial areas. Note
that when the motors are installed in residential
areas, supplementary measures may be required as
the motors may cause radio interference.
Immunity: The motor fulfils the requirements for
industrial areas.
Contact Grundfos for further information.
Enclosure class
Standard: IP44 (IEC 34-5).
Insulation class
F (IEC 85).
Standby power consumption
5-10 W.
Motor
[kW]
Emission category
2900-4000 min
-1
0.25
C2
0.37
C2
0.55
C2
0.75
C2
1.1
C2
1.5
C2
2.2
C2
3
C2
4
C2
5.5
C2