3.2 Electrical connection

A fuse has to be integrated into the power supply 
circuit. Use a 250 V AC, 0.032 A fine-wire fuse 
(slow-acting) in accordance with IEC 60127.

The whole cabinet, which the ALR 20/A Ex and 
its fuse is part of, must be equipped with a circuit 
breaker according to IEC 60947-2 or an 
equipment switch according to IEC 60947-3.

Carry out the electrical connections according to 
local regulations.
For all electrical connections see fig. 

1

.

Fig. 1

Electrical connections

3.2.1 Connection of main power supply

The power supply has to be connected with terminal 
2 and 10 according to the label on the cover. Use 
adequate wires for main power supply.

3.2.2 Connection of relay contacts

A change-over switch acts as output signal. 
According to the marking the maximum switching 
current is 5 A.

Relay outputs

3.2.3 Leakage sensor connections

The sensor cable leads 21 and 22 have to be 
connected to the light blue terminal 5 and 7. For 
additional extension a screened cable should be 
used. The maximum length of the cable from 
ALR 20/A Ex to leakage sensor is 50 m. 
As an alternative to forward the signal over longer 
distances (> 50 m), use the potential-free outputs 
(terminal 1 and 4).

CAUTION

Electric shock

Minor or moderate personal injury
- Switch off the power supply before you 

start any work on the product.

- Make sure that the power supply cannot 

be accidentally switched on.

TM0

7

 0

97

1 0

9

1

9

Terminal

Function

2 (A1)

Power supply (L - phase)

10 (A2)

Power supply (N - neutral)

1-3; 1-4

Relay outputs

5-7 (clamp light blue)

Sensor

21

22

L N

Operation

Relay function

No leakage 

detected

Relay contact 1-4 closed

Relay contact 1-3 open

Leakage 
detected

Relay contact 1-4 open

Relay contact 1-3 closed

If the feed cable is being extended, follow 
the ATEX-directives, standards EN 60079-
11 and EN 60079-14 to maintain the 
intrinsic safe circuit. 
For intrinsically safe and nonintrinsically 
safe circuits the clamp connections must 
be separated and marked unmistakably. 
The operator has to make sure that all 
installation works are done in conformity 
with the relevant standards.

Summary of Contents for ALR 20/A Ex

Page 1: ...ALR 20 A Ex relay Installation and operating instructions 50 60 Hz GRUNDFOS INSTRUCTIONS ALR 20 A Ex relay http net grundfos com qr i 99421246...

Page 2: ...scription 6 7 2 Applications 6 7 3 Intended use 6 7 4 Approvals 7 7 5 Nameplate 7 8 Servicing the product 7 8 1 Replacing the product 7 9 Technical data 8 9 1 Operating conditions of ALR 20 A Ex 8 9 2...

Page 3: ...nnection 3 Carry out the electrical connection See also section 9 Technical data The ALR 20 A Ex must only be used together with leakage sensor type AL05 Ex Installation must be carried out by qualifi...

Page 4: ...inal 5 and 7 For additional extension a screened cable should be used The maximum length of the cable from ALR 20 A Ex to leakage sensor is 50 m As an alternative to forward the signal over longer dis...

Page 5: ...ll be compared with a manually adjustable switch point If the limit of this switch point is exceeded the relay will switch to error mode Also in case of a short circuit or a cable break the relay will...

Page 6: ...iginal packaging to protect the product against moisture and heat Storage temperature 20 to 40 C After long periods of storage carry out a visual inspection of the product to make sure there is no moi...

Page 7: ...ts applicable to the equipment in this group 2 Equipment category according to the ATEX directive defining the requirements applicable to the equipment in this category G Explosive atmospheres caused...

Page 8: ...hing voltage 250 V AC 24 V DC 9 2 15 Maximum switching current 5 A 9 2 16 Maximum switching capacity 100 VA 100 W 9 2 17 Electrical life cycle 100 000 switching cycles at maximum load 9 2 18 Mechanica...

Page 9: ...tto la sua esclusiva responsabilit che il prodotto ALR 20 A Ex relay and AL05 Ex sensor al quale si riferisce questa dichiarazione conforme alle seguenti direttive del Consiglio riguardanti il riavvic...

Page 10: ...S Directives 2011 65 EU and 2015 863 EU Standard used EN IEC 63000 2018 Low voltage directive 2014 35 EU Applies only products with sensor and relay Standards used IEC 61010 1 2010 IEC 61010 1 2010 AM...

Page 11: ...ndfos d clarons sous notre seule responsabilit que les produits auxquels se r f re cette d claration sont conformes aux lois ordonnances normes et sp cifications marocaines pour les quelles la conform...

Page 12: ...12...

Page 13: ...10 A EH TKAM L 0342 321 69 66 0532 698 69 66 0342 321 69 61 MEHMET DUMAN mduman asinteknoloji com tr ARI MOTOR STANBUL ORHANLI MESC T MH DEMOKRAS CD B RMES SAN S T A 3 BLOK NO 9 TUZLA STANBUL 0216 39...

Page 14: ...50 51 51 E mail info_GDK grundfos com www grundfos com DK Estonia GRUNDFOS Pumps Eesti O Peterburi tee 92G 11415 Tallinn Tel 372 606 1690 Fax 372 606 1691 Finland OY GRUNDFOS Pumput AB Trukkikuja 1 F...

Page 15: ...ozsk 4D 821 09 BRATISLAVA Phona 421 2 5020 1426 sk grundfos com Slovenia GRUNDFOS LJUBLJANA d o o Lesko kova 9e 1122 Ljubljana Phone 386 0 1 568 06 10 Telefax 386 0 1 568 06 19 E mail tehnika si grund...

Page 16: ...2268 Trademarks displayed in this material including but not limited to Grundfos the Grundfos logo and be think innovate are registered trademarks owned by The Grundfos Group All rights reserved 2020...

Reviews: