background image

English (GB)

7

7.4 Approvals

The product has been tested by Eurofins.

7.4.1 Ex approval standards

Leakage sensor relay ALR 20/A Ex marking

 II (2)G [Ex ib Gb] IIC

Leakage sensor AL05 Ex marking

 II 2G Ex db ib IIC T4 Gb

IECEx certificate No: IECEx SEV 18.0008X
Standards: IEC 60079-0:2017, IEC 60079-1:2014, 
IEC 60079-11:2011

7.5 Nameplate

Fig. 4

Nameplate of ALR 20/A Ex relay

8. Servicing the product

The ALR 20/A Ex requires no maintenance. It may 
only be cleaned with a dustless cloth.

8.1 Replacing the product

Replace the ALR 20/A Ex in case of a fault.
See section 

3. Installing the product

.

Directive/
standard

Code Description

ATEX

Marking of explosion 
protection

II

Equipment group according 
to the ATEX directive, 
defining the requirements 
applicable to the equipment 
in this group

2

Equipment category 
according to the ATEX 
directive, defining the 
requirements applicable to 
the equipment in this 
category

G

Explosive atmospheres 
caused by gases, vapours or 
mists

Harmonised 
European 
standard

Ex

The equipment conforms to 
the harmonised European 
standard.

db

Leakage sensor can be part 
of flameproof enclosure 
according to EN 60079-1

ib

Intrinsic safety according to 
EN 60079-11.

IIC

Classification of gases, see 
EN 60079-0.
Gas group C.

T4

Maximum surface 
temperature is 135 °C

Gb

Equipment protection level. 
This product is suitable for 
zone1 or zone 2

TM

07

 41

0

1

 09

19

Pos.

Description

1

Manufacturer

2

Ex description 

3

Type identification

4

Certificate number ATEX/IECEx

WARNING

Electric shock

Death or serious personal injury
- Switch off the power supply before you 

start any work on the product.

- Make sure that the power supply cannot 

be accidentally switched on.

1

2

3

4

Summary of Contents for ALR 20/A Ex

Page 1: ...ALR 20 A Ex relay Installation and operating instructions 50 60 Hz GRUNDFOS INSTRUCTIONS ALR 20 A Ex relay http net grundfos com qr i 99421246...

Page 2: ...scription 6 7 2 Applications 6 7 3 Intended use 6 7 4 Approvals 7 7 5 Nameplate 7 8 Servicing the product 7 8 1 Replacing the product 7 9 Technical data 8 9 1 Operating conditions of ALR 20 A Ex 8 9 2...

Page 3: ...nnection 3 Carry out the electrical connection See also section 9 Technical data The ALR 20 A Ex must only be used together with leakage sensor type AL05 Ex Installation must be carried out by qualifi...

Page 4: ...inal 5 and 7 For additional extension a screened cable should be used The maximum length of the cable from ALR 20 A Ex to leakage sensor is 50 m As an alternative to forward the signal over longer dis...

Page 5: ...ll be compared with a manually adjustable switch point If the limit of this switch point is exceeded the relay will switch to error mode Also in case of a short circuit or a cable break the relay will...

Page 6: ...iginal packaging to protect the product against moisture and heat Storage temperature 20 to 40 C After long periods of storage carry out a visual inspection of the product to make sure there is no moi...

Page 7: ...ts applicable to the equipment in this group 2 Equipment category according to the ATEX directive defining the requirements applicable to the equipment in this category G Explosive atmospheres caused...

Page 8: ...hing voltage 250 V AC 24 V DC 9 2 15 Maximum switching current 5 A 9 2 16 Maximum switching capacity 100 VA 100 W 9 2 17 Electrical life cycle 100 000 switching cycles at maximum load 9 2 18 Mechanica...

Page 9: ...tto la sua esclusiva responsabilit che il prodotto ALR 20 A Ex relay and AL05 Ex sensor al quale si riferisce questa dichiarazione conforme alle seguenti direttive del Consiglio riguardanti il riavvic...

Page 10: ...S Directives 2011 65 EU and 2015 863 EU Standard used EN IEC 63000 2018 Low voltage directive 2014 35 EU Applies only products with sensor and relay Standards used IEC 61010 1 2010 IEC 61010 1 2010 AM...

Page 11: ...ndfos d clarons sous notre seule responsabilit que les produits auxquels se r f re cette d claration sont conformes aux lois ordonnances normes et sp cifications marocaines pour les quelles la conform...

Page 12: ...12...

Page 13: ...10 A EH TKAM L 0342 321 69 66 0532 698 69 66 0342 321 69 61 MEHMET DUMAN mduman asinteknoloji com tr ARI MOTOR STANBUL ORHANLI MESC T MH DEMOKRAS CD B RMES SAN S T A 3 BLOK NO 9 TUZLA STANBUL 0216 39...

Page 14: ...50 51 51 E mail info_GDK grundfos com www grundfos com DK Estonia GRUNDFOS Pumps Eesti O Peterburi tee 92G 11415 Tallinn Tel 372 606 1690 Fax 372 606 1691 Finland OY GRUNDFOS Pumput AB Trukkikuja 1 F...

Page 15: ...ozsk 4D 821 09 BRATISLAVA Phona 421 2 5020 1426 sk grundfos com Slovenia GRUNDFOS LJUBLJANA d o o Lesko kova 9e 1122 Ljubljana Phone 386 0 1 568 06 10 Telefax 386 0 1 568 06 19 E mail tehnika si grund...

Page 16: ...2268 Trademarks displayed in this material including but not limited to Grundfos the Grundfos logo and be think innovate are registered trademarks owned by The Grundfos Group All rights reserved 2020...

Reviews: