Ensure that the
FireSAFE
is positioned to allow access for examination and service. A
minimum of 50cm should be left all around the
FireSAFE
unit.
Adequate drainage facilities and protection from water damage in the immediate
vicinity of the
FireSAFE
unit must be provided.
If the
FireSAFE
unit is installed into a roof spaces, then provisions should be made for
the small level of vibration associated with any rotating equipment in case it causes
disturbance. Provision should also be made for drainage of the unit, leakage and any loss of
water during commissioning and service.
The
FireSAFE
unit should not be installed in an unventilated small space, ensure
adequate ventilation for the motor.
8.8 Breaktanks and mains water connection
In some situations, and with the permission of the Water Utility company, it may be
possible to connect the
FireSAFE
unit directly to the town water mains. A dedicated
suction pipe will be required, the diameter of which should match the pump suction as an
absolute minimum.
In situations where the town mains supply cannot be utilised directly it will be necessary to
install a water storage tank (break tank) between the incoming mains water supply and the
FireSAFE
unit, it must however have a type AB Air Gap and be supplied and installed in
accordance with the Water Byelaws Regulations. Grundfos can offer a suitable break tank.
Check that the water storage tank has adequate capacity to meet/exceed the demand.
8.9
Installation general requirements
The suction and discharge pipework must be at least the same size as the
FireSAFE
suction and discharge ports, as a smaller size may result in reduced pump performance
or increased system resistance leading to a reduced flow.
The installation suction and discharge pipework may need to be properly supported
before
being connected to the
FireSAFE
unit so that the
FireSAFE
unit is not stressed.
The pipework installation to and from the
FireSAFE
unit should be in accordance with
local water authority regulations, best industry practice and according to the design
recommendations in BS 9251 latest revision.
The electrical installation of the
FireSAFE
unit should be in accordance with the latest
issue of the I.E.E. regulations and according to BS 9251 latest revision.