Filtration/Deacidification
Filter systems GENO-mat KF-Z / MS-Z / AK-Z
Deacidification systems GENO-mat TE-Z
Order no. 035 129 950-inter Edited by: nkes-mrie G:\BA-129950-INTER_035_FILTERANLAGEN_GENO-MAT.DOCX
30
G Maintenance and Care
1 | Basic information
In order to guarantee the reliable function of filter/deacidification sys-
tems over a long period of time, some maintenance work has to be
performed at regular intervals. This applies in particular to the back-
wash in the drinking water sector where the required measures are
defined in the pertinent regulations and guidelines. All regulations
and guidelines which apply at the installation site must be strictly
adhered to.
DIN EN 806-5 stipulates:
Inspection every 2 months
Maintenance every 6 months
Maintenance must be performed by the Gr
ü
nbeck
’
s customer
service/authorised service company or by a specialised company.
An operation log must be kept in order to document the mainte-
nance work performed.
Note:
A maintenance contract ensures that all the required mainte-
nance work will be performed in due time.
The operation log is attached to this operation manual.
2 | Inspection (functional check)
You may perform the regular inspections yourself.
Summary: Inspection work
Determine system pressure differential
Check controller settings:
a) Time
b) Check backwash interval
Note:
Minor deviations are normal and cannot be prevented techni-
cally. If you detect major deviations, please contact Gr
ü
nbeck
’
s cus-
tomer service/authorised service company.
Check the entire system for outward tightness.
Check control valve to drain for tightness (in operating mode).