Filtration/Deacidification
Filter systems GENO-mat KF-Z / MS-Z / AK-Z
Deacidification systems GENO-mat TE-Z
Order no. 035 129 950-inter Edited by: nkes-mrie G:\BA-129950-INTER_035_FILTERANLAGEN_GENO-MAT.DOCX
26
E Start-up
The work described below may only be performed by trained ex-
perts. We recommend having the start-up performed by Gr
ü
nbeck
’
s
technical service/authorised service company.
Warning!
Danger of contamination due to stagnation! According to
VDI 6023, filling the system with drinking water before normal opera-
tion commences is prohibited.
The GENO-mat
filter/deacidification systems must therefore first be
connected to the drinking water system immediately prior to com-
missioning.
1 | How to start up the system
1. Open the valve at the raw water inlet.
2. Open the valve at the pure water outlet.
3. Perform a visual check. Ensure that no water leaks from the sys-
tem anywhere.
4. Rinse out fine particles
The filter material contains a small amount of fine particles which
must be flushed by means of a backwash prior to start-up. Re-
lease a manual regeneration
(refer to chapter F, item 1.4).
Note:
The backwash process must be repeated until the backwash
water that flows to the drain in the process step
„
first filtrate
“
is
clear.
5. Take a water sample at the sampling valve downstream of the
system.
6. Determine the iron concentration by means of the water test kit.
7. Fill in the cover sheet and column 1 in the operation log.