Filtration/Deacidification
Filter systems GENO-mat KF-Z / MS-Z / AK-Z
Deacidification systems GENO-mat TE-Z
Order no. 035 129 950-inter Edited by: nkes-mrie G:\BA-129950-INTER_035_FILTERANLAGEN_GENO-MAT.DOCX
31
3 | Maintenance
Maintenance work on the filter/deacidification systems may only be
performed by Gr
ü
nbeck
’
s technical service/authorised service com-
pany or by an approved specialist.
An operation log must be kept for the filter/deacidification systems.
In this operation log, the customer service technician records all
maintenance and repair work performed. In case of malfunctions,
this log helps to identify possible sources of error. In addition the log
documents the proper system maintenance.
Make sure that all maintenance work is recorded
in the operation log.
Summary: Maintenance work
Read water pressure, flow pressure and if necessary water meter
reading.
Check release of backwash.
Check control valve for tightness, replace wearing seals if neces-
sary, check the proper function of the drive motor of the control
valve, clean injector and sieve.
Disinfect the system if required.
Check the level of the filter material in the filter tank. If necessary,
refill the filler material.
3.1 Disinfecting the GENO-mat filter/deacidification systems
Note:
We recommend having the disinfection performed by
Grünbeck’s authorised technical service/authorised service compa-
ny.