Filtration/Deacidification
Filter systems GENO-mat KF-Z / MS-Z / AK-Z
Deacidification systems GENO-mat TE-Z
Order no. 035 129 950-inter Edited by: nkes-mrie G:\BA-129950-INTER_035_FILTERANLAGEN_GENO-MAT.DOCX
28
Backwash wheel
Button to set the time
Hour wheel
Reference arrow for current time and operating state
(black)
Reference arrow (red)
Reference point for operating state (white)
Day disk
Steel switching pin (in home position
moved to centre point, in switch position
moved outwards)
Fig. F-1: Control unit and operating elements
„
front view
“
2. Push the switching pin (Fig. F-1, Item 5) outwards for the 1st day.
3. Set the other switching pins as required.
On all days where the switching pins are pushed outwards, the
backwash is released. In order to set, for example, a backwash in-
terval of 3 days, the switching pins in positions 1, 4, 7 and 10 on the
day disk must be pushed outwards (Fig. F-1, Item 4).