67
3.4
Flow chart impulse mode PUL
The adjoining figure shows the basic flow
chart for control signal 2 seconds (chapter
8.2.1) which triggers a stroke in impulse
mode as well as possible errors.
The flow chart shall help you creating a
customized program for your external
control (PLC). This program is essential
to completely control and run LUB-V
properly.
Both PIN 2 and 4 refer to the electrical
interface M12x1 (chapter 8.1)
Proceed the same way when creating
a program to trigger the FIL function
(chapter 8.2.2) but change control signal
2 seconds to control signal 12 seconds.
Start
PIN 4
>3 seconds high?
Sending control signal
2 seconds
to PIN 2
Control signal not
detected correctly
PIN 4
falling edge?
PIN 4
rising edge
after 7...17
seconds?
PIN 4
>3 seconds high?
PIN 4
0,5Hz squarewave
signal?
PIN 4
>3 seconds low?
Error E2
or E3?
Error E4?
PIN 4
rising edge
after 10...11
seconds?
PIN 4
>3 seconds high?
Lubrication
successful
Lubrication not
successful. Error E1;
empty cartridge
Lubrication not
successful. Error
E2...E4
Start
Change cartridge
Read displayed error
message
Disassemble LUB-S
and return it to the
manufacturer
Control signal
14 seconds
to PIN 2
Produce relief
no
yes
no
yes
no
no
yes
no
no
yes
yes
yes
no
yes
yes
yes
no
no
yes