Page 9
MAC ADDRESS
0001CE20001
ADV-C2-MLT-00000001
Tamper
1
2
3
4
Rev
Load/Clear
Status
Reset
!
!
Optical
Tamper
MP 0V
GND
12V
8A
MAX
12V 5A MAX
A B S
RS-485
ADVANCE
Connect 12V external power supply, if used.
Select the most appropriate option: either
5A (2.1mm circular jack) or 8A (4-pin screw
terminal).
Connect the IP and/or RS485 cable as
required, please note for all controller
configuration IP must be connected first.
Snap in Blades. Ensure all
required Blades are inserted
before power is applied.
For
Door Blade
connections,
For
I/O Blade
connections,
For
OSDP Blade
connections, see page 14
Run cabling to the enclosure from all the
doors, readers, locks, inputs and outputs
that are to be connected.
The controller can be installed in a
Grosvenor enclosure or a third-party
enclosure.
Attach the enclosure to the wall using the
fixing points. Install the controller in the
enclosure. Connect the physical tamper.
The built-in optical tamper operates
automatically when the enclosure is closed.
Connect a 12V lead-acid
back-up battery if required.
Once power is applied to the controller
it will be visible to the Janus C4
Configurator application.
1
2
2
3
3
4
4
5
5
6
6
Setting up