PLUMBING INSTALLATION
© 2013 Greenwood Clean Energy, Inc All Rights Reserved V1.9
Page 27
Nonstandard Installs
Q: If the Frontier CX is installed without the factory mounted Hydronic Conditioning Manifold and Overheat
Cooling Kit what piping and components are required?
The Frontier CX Hydronic Conditioning Manifold and ThermSafe
TM
Overheat Cooling Kit simplifies the
installation by including many of the components that typically must be installed in the boiler loop. The
Hydronic components are custom designed for the Frontier Series, factory calibrated and preset to ensure
optimum performance.
For the rare situation in which the Frontier CX is installed without the install package (this will void the
warranty without prior approval in writing from Greenwood Clean Energy), the installer must design, source,
and install components to meet the following requirements:
Hydronic System Functionality
Frontier CX
with install
package
Without
install
package
Requirements
Frontier Series Boiler Control System
Outlet temperature monitoring
Inlet temperature monitoring
Flow switch cabling
ThermSafe
TM
Overheat Cooling
connection ready
On-Demand Zone connection ready
Boiler loop circulation
X
Taco 007 circulator or equivalent UL rated
cirulator and piping to ensure 10 GPM (+- 2
GPM) flow rate
Flow rate stability
X
Hydraulic separation of boiler and
distribution loops
Air elimination
X
Air vent
Pressure relief
X
Atmosheric venting, pressure relief valve
Fluid fill
X
Boiler drain
Low temperature protection
X
Thermostatic 3-way 1" mixing valve
Cavitation protection
X
Boiler loop design that ensures sufficient
head at the circulator inlet
Low fluid protection
X
McDonnel & Miller FS-251 flow switch or
equivalent UL rated device
Power failure and overheat protection
X
Taco 1" normally open Zone Sentry valve,
power supply, gravity loop design, and
piping
Summary of Contents for Frontier CX
Page 1: ......
Page 3: ...This page intentionally left blank...
Page 4: ......
Page 8: ...SAFETY Page 4 2013 Greenwood Clean Energy Inc All Rights Reserved V1 9 SAFETY WARNINGS LABEL...
Page 9: ...SAFETY 2013 Greenwood Clean Energy Inc All Rights Reserved V1 9 Page 5 LABEL LOCATIONS...
Page 30: ...PLUMBING INSTALLATION Page 26 2013 Greenwood Clean Energy Inc All Rights Reserved V1 9...
Page 35: ...WIRING 2013 Greenwood Clean Energy Inc All Rights Reserved V1 9 Page 31...
Page 54: ...WA This page intentionally left blank...
Page 56: ...This page intentionally left blank...