111
Air to Water Heat Pump
Service Manual- Versati Series
NBJOUFOBODF
3.1.6 Compressor current protection(code:"P5") ; Compressor motor desynchronizing(code:"H7") ; IPM
protection(code:"H5"); Phase loss(code:"Ld")
E5 is displayed on
the wired controller
Is the compress
wire phase
sequence right?
Is the compress
wire terminals tightened?
adjust the compress
phase sequence
Tighten the
compressor
wire terminals
Replace the mainboard.
Does it work normally?
Replace
the compressor
P5
、
H7
、
H5 or Ld
is displayed in the
mainboard 88
Indicating Lamp
Yes
No
Work Normally
Yes
Yes
No
No
3.1.7 Charging circuit error(code:"PU")
E5 is displayed on
the wired controller
PU is displayed in
the mainboard 88
Indicating Lamp
Is the PFC wire
tightened or is the
sequence right?
Tighten the PFC wire
or adjust the sequence
Replace
the mainboard
Yes
No
Work Normally
Summary of Contents for VERSATI SERIES
Page 1: ...AIR TO WATER HEAT PUMP SERVICE MANUAL VERSATI SERIES T1 R410A 50Hz 60Hz GC201202 ...
Page 4: ...1 Air to Water Heat Pump Service Manual Versati Series PRODUCT QSPEVDU ...
Page 15: ...12 Air to Water Heat Pump Service Manual Versati Series CONTROL DPOUSPM ...
Page 66: ...63 Air to Water Heat Pump Service Manual Versati Series INSTALLATION JOTUBMMBUJPO ...
Page 92: ...89 Air to Water Heat Pump Service Manual Versati Series JOTUBMMBUJPO GRS CQ16Pd Na H ...
Page 102: ...99 Air to Water Heat Pump Service Manual Versati Series MAINTENANCE NBJOUFOBODF ...
Page 128: ...125 Air to Water Heat Pump Service Manual Versati Series NBJOUFOBODF Fig 14 ...
Page 158: ...JF00300495 ...