Air to Water Heat Pump
Service Manual- Versati Series
JOTUBMMBUJPO
ĸ
If the noise of the pump is not acceptable, we recommended change the default speed to medium
VSHHGEXWWRVHFXUHHQRXJKÀRZUDWHGRQRWVHWZDWHUVSHHGDV³0LQ´LWFDQOHDGXQH[SHFWHGÀRZUDWHHUURU
“EC”;
(2) Water Volume and Expansion Vessel Pressure
Note:
ķ
Expansion vessel is included which 10 liter and 1bar pre-pressure.
ĸ
Total water volume of 280 liter is default; If total water is changed because of installation condition, the
pre-pressure should be adjusted to secure proper operation. If the indoor unit is located at the highest position,
adjustment is not required;
Ĺ
Minimum total water volume is 20 liter;
ĺ
7RDGMXVWSUHSUHVVXUHXVHQLWURJHQJDVE\FHUWL¿FDWHGLQVWDOOHU
1.5 The method of calculating the charging pressure of expansion vessel needed to be adjusted is as
follows.
During installation, if the volume of water system has changed, please check if the pre-set pressure of the
expansion vessel needs to be adjusted according to the following formula:
P
g
=(H/10+0.3) Bar (H ---the difference between installing location of indoor unit and the highest spot of
water system.)
(QVXUHWKDWWKHYROXPHRIZDWHUV\VWHPLVORZHUWKDQWKHPD[LPXPYROXPHUHTXLUHGLQWKHDERYH¿JXUH,ILW
exceeds the range, the expansion vessel does not meet the installing requirement.
Installation height difference
1
Water volume
<280L
>280L
<7 m
Adjustment is not necessary
1. Pre-set pressure needs to be adjusted
according to the above formula.
2. Check if the water volume is lower than
the maximum water volume. (with help of
WKHDERYH¿JXUH
>7 m
1. Pre-set pressure needs to be adjusted
according to the above formula.
2. Check if the water volume is lower than
the maximum water volume. (with help of
WKHDERYH¿JXUH
The expansion vessel is too small and
adjustment is not available.
1
Note
:
Installation height difference: the difference between installing location of indoor unit and the highest spot of
water system; if the indoor unit is located at the highest point of the installation, the installation height difference
is considered 0m.
The minimum volume of the water system is 20 L.
Example 1: The indoor unit is installed 5m below the outdoor unit and the total volume of the water system
is 100L.
5HIHUULQJWRWKHDERYH¿JXUHLWLVQRWQHFHVVDU\WRDGMXVWWKHSUHVVXUHRIWKHH[SDQVLRQYHVVHO
Summary of Contents for VERSATI SERIES
Page 1: ...AIR TO WATER HEAT PUMP SERVICE MANUAL VERSATI SERIES T1 R410A 50Hz 60Hz GC201202 ...
Page 4: ...1 Air to Water Heat Pump Service Manual Versati Series PRODUCT QSPEVDU ...
Page 15: ...12 Air to Water Heat Pump Service Manual Versati Series CONTROL DPOUSPM ...
Page 66: ...63 Air to Water Heat Pump Service Manual Versati Series INSTALLATION JOTUBMMBUJPO ...
Page 92: ...89 Air to Water Heat Pump Service Manual Versati Series JOTUBMMBUJPO GRS CQ16Pd Na H ...
Page 102: ...99 Air to Water Heat Pump Service Manual Versati Series MAINTENANCE NBJOUFOBODF ...
Page 128: ...125 Air to Water Heat Pump Service Manual Versati Series NBJOUFOBODF Fig 14 ...
Page 158: ...JF00300495 ...