27
Air to Water Heat Pump
Service Manual- Versati Series
DPOUSPM
The table of user function parameter
Code
Function description
Detail
Range
1
Setting interval of defrost mode
/
30~60minute(default:50)
2
Setting duration of defrost mode
/
1~15minute(default:10)
3
Setting enter temperature of preventing freezing
operation
/
1~5 (default:3 )
4
Setting exit temperature of preventing freezing operation
/
6~14 (default:12 )
5
Setting enter temperature of anti-high temperature
operation
/
55~60 (default:58 )
6
Setting exit temperature of anti-high temperature
operation
/
40~54 (default:53 )
7
Setting enter temperature of defrost operation
/
-10~0 (default:-4 )
8
Setting exit temperature of defrost operation
/
5~30 (default:15 )
3.2.3.6. Set target temperature
1) Press
button or
button to turn on the unit.
2) Press repeatedly
button to select one target temperature:
room temperature,
RXWÀRZZDWHUWHPSHUDWXUH
sanitary water tank temperature,
DQGVRODURXWÀRZZDWHUWHPSHUDWXUH
The setting temperature is blinking.
Summary of Contents for VERSATI SERIES
Page 1: ...AIR TO WATER HEAT PUMP SERVICE MANUAL VERSATI SERIES T1 R410A 50Hz 60Hz GC201202 ...
Page 4: ...1 Air to Water Heat Pump Service Manual Versati Series PRODUCT QSPEVDU ...
Page 15: ...12 Air to Water Heat Pump Service Manual Versati Series CONTROL DPOUSPM ...
Page 66: ...63 Air to Water Heat Pump Service Manual Versati Series INSTALLATION JOTUBMMBUJPO ...
Page 92: ...89 Air to Water Heat Pump Service Manual Versati Series JOTUBMMBUJPO GRS CQ16Pd Na H ...
Page 102: ...99 Air to Water Heat Pump Service Manual Versati Series MAINTENANCE NBJOUFOBODF ...
Page 128: ...125 Air to Water Heat Pump Service Manual Versati Series NBJOUFOBODF Fig 14 ...
Page 158: ...JF00300495 ...