Air to Water Heat Pump
Service Manual- Versati Series
JOTUBMMBUJPO
2). GRS-CQ16Pd/Na-H(I)
Expansion bolt
Install wall
ʽ
CAUTION!
While lifting the indoor unit, at least two persons should be joined. Weight of the indoor unit is almost 52kg.
Precautions on Installation of Indoor Unit
1
Indoor unit shall be vertically mounted on the wall of the room with expansion bolt.
2
Keep the Indoor unit away from heat sources such as heat sink and so on in the room as much as
possible.
3
Keep the indoor unit as close as possible to outdoor unit. Level distance between connection pipes can
not exceed 30m and vertical distance can not exceed 15m.
1.3.3 Installation of Insulated Water Tank
1.3.3.1 Installation Measure
The insulated water tank should be installed and keep levelly within 5m and vertically within 3m from the
Indoor unit. It can be installed in the room.
Standing water tank must be installed vertically with the bottom on the ground, never suspended.
Installation place must be firm enough and the water tank should be fixed on the wall with bolts to avoid
vibration, as shown in the following figure. Weight capacity of water tank during installation should also be
considered.
Fix
with
bolts
Water tank
Installed on the ground and never suspended
Summary of Contents for VERSATI SERIES
Page 1: ...AIR TO WATER HEAT PUMP SERVICE MANUAL VERSATI SERIES T1 R410A 50Hz 60Hz GC201202 ...
Page 4: ...1 Air to Water Heat Pump Service Manual Versati Series PRODUCT QSPEVDU ...
Page 15: ...12 Air to Water Heat Pump Service Manual Versati Series CONTROL DPOUSPM ...
Page 66: ...63 Air to Water Heat Pump Service Manual Versati Series INSTALLATION JOTUBMMBUJPO ...
Page 92: ...89 Air to Water Heat Pump Service Manual Versati Series JOTUBMMBUJPO GRS CQ16Pd Na H ...
Page 102: ...99 Air to Water Heat Pump Service Manual Versati Series MAINTENANCE NBJOUFOBODF ...
Page 128: ...125 Air to Water Heat Pump Service Manual Versati Series NBJOUFOBODF Fig 14 ...
Page 158: ...JF00300495 ...