GREE Duct type Ducted Type Split Air-Conditioner Units
94
(24) “dC” Capacity DIP switch setting error
Error display: wired controller of
IDU and the dash receiver of IDU will display
.
Error judgment condition and method:
If capacity DIP switch is set to the wrong position, report the error.
Possible reason
:
1) Capacity DIP switch is set to the wrong position.
2) Detecting circuit is abnormal.
(25) “db” Project debugging
Error display:
ODU mainboard, IDU displays
.
Error judgment condition and method:
This is a status code of project debugging, not a error
code. When IDU or ODU displays this code, it means the unit is under debugging status and the IDU
cannot be operated.
Troubleshooting: ——
Possible reason
:
——
(26) “E1” high pressure protection
Error display:
ODU mainboard, IDU displays
.
Applicable model:
all models.
Error judgment condition and method
:
Judge through detecting the real-time high pressure or the
high pressure switch. If the sensor detects that the high pressure value is over 65
℃
or the high pressure
switch is disconnected, then it is judged as high pressure, the system will stop the unit for protection.
Possible reason
:
1) Cut-off valve of ODU is not opened;
2) High pressure switch operation is abnormal;
3) Outdoor or indoor fan is abnormal;
4) Filter screen of IDU or air duct is blocked (heating mode);
5) Ambient operation temperature is too high;
6) Refrigerant charging of the system is too much;
7) System pipeline is blocked;
Summary of Contents for UM600PH/A-M
Page 4: ...4 PRODUCT...
Page 9: ...GREE Duct type Ducted Type Split Air Conditioner Units 9 CONTROL...
Page 25: ...GREE Duct type Ducted Type Split Air Conditioner Units 25 2 Click Next...
Page 49: ...GREE Duct type Ducted Type Split Air Conditioner Units 49...
Page 56: ...GREE Duct type Ducted Type Split Air Conditioner Units 56 INSTALLATION...
Page 72: ...GREE Duct type Ducted Type Split Air Conditioner Units 72 DEBUGGING MAINTENANCE...
Page 116: ...GREE Duct type Ducted Type Split Air Conditioner Units 116 UMLD400W A M P...
Page 118: ...GREE Duct type Ducted Type Split Air Conditioner Units 118 UM500PH A M P UM600PH A M P...
Page 121: ...JF00303352 JF00304250...