GREE Duct type Ducted Type Split Air-Conditioner Units
85
(3) “A4” oil return
Fault display:
the main board of outdoor unit and indoor unit will display
.
Applicable model:
all models.
Judgment condition and method for the fault
:
It is a status code, which means the system has
entered oil return status, if the oil returns under heating mode, the indoor fan will suspend for 5-10min.
Possible reason:
the load for the air conditioner is low, unit compressor has been operating in low
frequency for a long time.
Troubleshooting:
not faulted.
(4) “A6” cooling/heating function setting
Fault display:
the main board of outdoor unit will display
.
Applicable model:
all models.
Judgment condition and method for the fault
:
It is a status code, which means the system has
entered cooling/heating function setting status, at this time, choose cooling/heating (nA), cooling only
(nC), heating only (nH) and fan blow (nF) for setting.
Possible reason
:
——
Troubleshooting:
not faulted.
(5) “A7” quiet mode setting
Fault display:
the main board of outdoor unit will display
.
Applicable model:
all models.
Judgment condition and method for the fault
:
It is a status code, which means the system has
entered quiet mode setting status.
Judgment condition and method for the fault
:
——
Troubleshooting
:
——
(6) “AH” heating
Fault display:
the main board of outdoor unit will display
.
Applicable model:
all models.
Judgment condition and method for the fault
:
It is a status code, which means the system has
entered heating mode setting status.
Possible reason
:
——
Troubleshooting
:
——
(7) “AC” cooling
Fault display:
the main board of outdoor unit will display
.
Summary of Contents for UM600PH/A-M
Page 4: ...4 PRODUCT...
Page 9: ...GREE Duct type Ducted Type Split Air Conditioner Units 9 CONTROL...
Page 25: ...GREE Duct type Ducted Type Split Air Conditioner Units 25 2 Click Next...
Page 49: ...GREE Duct type Ducted Type Split Air Conditioner Units 49...
Page 56: ...GREE Duct type Ducted Type Split Air Conditioner Units 56 INSTALLATION...
Page 72: ...GREE Duct type Ducted Type Split Air Conditioner Units 72 DEBUGGING MAINTENANCE...
Page 116: ...GREE Duct type Ducted Type Split Air Conditioner Units 116 UMLD400W A M P...
Page 118: ...GREE Duct type Ducted Type Split Air Conditioner Units 118 UM500PH A M P UM600PH A M P...
Page 121: ...JF00303352 JF00304250...