GREE Duct type Ducted Type Split Air-Conditioner Units
92
Error judgment condition and method:
Sample the AD value of temperature sensor through
temperature sensor detecting circuit and judge the range of AD value, if the sampling AD value exceeds
upper limit and lower limit in 5 seconds continuously, report the error.
Possible reason
:
1) Poor contact between ambient temperature sensor and terminal in mainboard interface.
2) Ambient temperature sensor is abnormal.
3) Detecting circuit is abnormal
.
(20) “d4” Inlet pipe temperature sensor error
Error display:
wired controller of
IDU and the dash receiver of IDU will display
.
Error judgment condition and method:
Sample the AD value of temperature sensor through
temperature sensor detecting circuit and judge the range of AD value. If the sampling AD value exceeds
upper limit and lower limit in 5 seconds continuously, report the error.
Possible reason
:
1) Poor contact between inlet pipe temperature sensor and terminal in mainboard interface.
2) Inlet pipe temperature sensor is abnormal.
3) Detecting circuit is abnormal.
(21) “d5” midst pipe temperature sensor error
Error display:
IDU displays
.
Applicable mode:
all indoor units.
Error judgment condition and method:
Sample the AD value of temperature sensor through
temperature sensor detecting circuit and judge the range of AD value. If the sampling AD value exceeds
upper limit and lower limit in 5 seconds continuously, report the error.
Possible reason
:
1) Poor contact between midst pipe temperature sensor and terminal in mainboard interface.
2) Midst pipe temperature sensor is abnormal.
3) Detecting circuit is abnormal.
Summary of Contents for UM600PH/A-M
Page 4: ...4 PRODUCT...
Page 9: ...GREE Duct type Ducted Type Split Air Conditioner Units 9 CONTROL...
Page 25: ...GREE Duct type Ducted Type Split Air Conditioner Units 25 2 Click Next...
Page 49: ...GREE Duct type Ducted Type Split Air Conditioner Units 49...
Page 56: ...GREE Duct type Ducted Type Split Air Conditioner Units 56 INSTALLATION...
Page 72: ...GREE Duct type Ducted Type Split Air Conditioner Units 72 DEBUGGING MAINTENANCE...
Page 116: ...GREE Duct type Ducted Type Split Air Conditioner Units 116 UMLD400W A M P...
Page 118: ...GREE Duct type Ducted Type Split Air Conditioner Units 118 UM500PH A M P UM600PH A M P...
Page 121: ...JF00303352 JF00304250...