GREE Duct type Ducted Type Split Air-Conditioner Units
99
Troubleshooting
:
1) Replace the small CPU board.
2) Replace the control board.
3) Replace the control board.
(29) “F5” malfunction of discharge temperature sensor for compressor 1
Error display:
the main board of outdoor unit and indoor unit will display
.
Applicable model:
all outdoor units.
Error judgment condition and method
:
Sample the AD value of temperature sensor through
temperature sensor detecting circuit and judge the range of AD value, if the sampling AD value exceeds
upper limit and lower limit in 30 seconds continuously, report the error.
Possible reason
:
1) Poor contact between discharge temperature sensor and terminal in mainboard interface.
2) The discharge temperature sensor is abnormal.
3) The detected circuit is abnormal.
Troubleshooting
:
Yes
“F5” discharge
temperature sensor error
of compressor 1
Re-insert it after proper
treatment
The detected circuit might
be abnormal
Yes
Replace the main control
board
No
Check the wiring terminal of the main board
and temperature sensor to see if it’s loose or
are there any foreign objects
No
Replace the temperature sensor
(30) “J7” air-mixing protection for 4-way valve
Error display:
the main board of outdoor unit and indoor unit will display
.
Applicable model:
heat pump models.
Error judgment condition and method
:
Detect system high and low pressure through pressure
sensor, start the unit, when the pressure difference of high and low pressure is less than 0.1MPa, the
unit will be stopped for protection.
Possible reason
:
1) Coil or connection wire is abnormal.
Summary of Contents for UM600PH/A-M
Page 4: ...4 PRODUCT...
Page 9: ...GREE Duct type Ducted Type Split Air Conditioner Units 9 CONTROL...
Page 25: ...GREE Duct type Ducted Type Split Air Conditioner Units 25 2 Click Next...
Page 49: ...GREE Duct type Ducted Type Split Air Conditioner Units 49...
Page 56: ...GREE Duct type Ducted Type Split Air Conditioner Units 56 INSTALLATION...
Page 72: ...GREE Duct type Ducted Type Split Air Conditioner Units 72 DEBUGGING MAINTENANCE...
Page 116: ...GREE Duct type Ducted Type Split Air Conditioner Units 116 UMLD400W A M P...
Page 118: ...GREE Duct type Ducted Type Split Air Conditioner Units 118 UM500PH A M P UM600PH A M P...
Page 121: ...JF00303352 JF00304250...