GREE Duct type Ducted Type Split Air-Conditioner Units
53
(4) Usage of converter configuring software:
1) When the converter is working, hold the button “SET” for 5 sec. Function LED will be
flickering, indicating that the converter has enter the baud rate setting mode. Then you can
use the converter configuring software to set the baud rate of converter. Baud rate
supported by the converter (baud rate of air conditioner’s communication interface
matches with the baud rate of USB interface automatically):
Ex-factory defaulted baud rate: (unit: bps)
AC is connected with
Baud rate of air conditioner interface
Baud rate of USB interface
CAN
20000/50000 self-adaptive
115200
HBS
57600
38400
RS485
9600
9600
Baud rate look-up table for RS485 interface (unit: bps)
RS485 interface
4800
9600
19200
38400
57600
115200
USB interface
4800
9600
19200
38400
57600
115200
Baud rate look-up table for HBS interface (unit: bps)
HBS interface
9600
19200
38400
57600
USB interface
4800
9600
19200
38400
Summary of Contents for UM600PH/A-M
Page 4: ...4 PRODUCT...
Page 9: ...GREE Duct type Ducted Type Split Air Conditioner Units 9 CONTROL...
Page 25: ...GREE Duct type Ducted Type Split Air Conditioner Units 25 2 Click Next...
Page 49: ...GREE Duct type Ducted Type Split Air Conditioner Units 49...
Page 56: ...GREE Duct type Ducted Type Split Air Conditioner Units 56 INSTALLATION...
Page 72: ...GREE Duct type Ducted Type Split Air Conditioner Units 72 DEBUGGING MAINTENANCE...
Page 116: ...GREE Duct type Ducted Type Split Air Conditioner Units 116 UMLD400W A M P...
Page 118: ...GREE Duct type Ducted Type Split Air Conditioner Units 118 UM500PH A M P UM600PH A M P...
Page 121: ...JF00303352 JF00304250...