91
H7
Error Code Diagnostics
H7 Error Code, continued on next page
Start Troubleshooting after unit
is powered off for 3 minutes
Are the compressor terminal
connected properly?
Yes
Correct wiring
problem
Remove Malfunction?
No
Replace Compressor
Replace Control Board AP1
No
End Troubleshooting
Desynchronizing of compressor
Status:
During cooling mode, compressor will stop,
indoor fan will run. Heating mode all units
stop.
1.
Check the resistance of the compressor
terminals and connections to the compressor
2.
Check for overcharge of refrigerant
3.
Check for correct voltage
Troubleshooting Procedure for Synchronizing Fault after Unit is Started
Yes
Compressor Terminals
Summary of Contents for TERRA09HP230V1A
Page 13: ...13 Product Introduction Operation Characteristic Curve ...
Page 14: ...14 Product Introduction Capacity Variation Ratio According to Temperature ...
Page 16: ...16 Noise Criteria Curve Tables Product Introduction ...
Page 54: ...54 Electrical Schematics ...
Page 135: ...135 Gree Electric Appliances Inc C 2014 Cat No DFS TERRA HP 2SM Version 2 0 ...