82
E6
Communication Failure
Status:
Cooling operation, compressor stops while
indoor fans runs. Heating operation, complete
unit stops
1.
Improper voltages
2.
Mis-matched indoor and outdoor units
3.
Improper wiring between indoor and outdoor
units
Error Code Diagnostics
E6 Error Code
Start Troubleshooting
Did the unit operate normally before
the error occurred?
Check for proper wiring of
indoor and outdoor units with
unit wiring diagram
Yes
Correct connections
Check factory wiring of indoor and
outdoor units
Is wiring damaged?
Repair wiring, fault is
detected with control
board voltage
End Troubleshooting
Are all connections
correct?
Did this correct the
problem?
Is system
operating properly
Yes
Yes
No
No
No
Yes
Communication circuit
problem?
No
Replace outdoor
main board AP11
Is system
operating properly
Replace indoor board
AP2
No
Yes
Yes
Yes
No
Yes
No