System Operation 18,000/24,000 btuh Models, cont.
Defrost Process, cont.
2) When heating has operated continuously for 45 minutes, or accumulated for 90 minutes, the unit will enter defrost
mode in 3 minutes after meeting any of the conditions below:
A. Outdoor ambient >= 410 F and outdoor coil <= 280 F
B. 280 F <= T
outdoor
ambient< 410 F, T
outdoor
tube <= 210 F
C. 230 F <= T
outdoor
ambient < 280 F <= T
outdoor
tube <= 180 F
D. 140 F <= T
outdoor
ambient < 230 F , T
outdoor
tube -T
compensation
<= (T
outdoor
ambient - 370 F)
3) During defrost, if run time for the compressor does not reach 3 minutes, the defrost cycle will not start for the next 2
hours. At that time the compressor stops operation and 30 seconds later the outdoor fan will stop. 30 seconds after this
the 4-way reversing valve will de-energized. Following another 30 second delay, the compressor will increase its speed for
defrosting. Defrosting will last for 450 seconds or until the T
outdoor
tube >= 500 F, at this temperature the compressor will
decrease it’s speed for 30 seconds, then will stop. In another 30 seconds the 4-way valve will energize, the 60 seconds later
the compressor and outdoor fan will start. The compressor speed for defrosting will be 85hz.
During Defrost mode, a H1 will be displayed on the indoor front panel display indicating the user selected mode has been
overridden and the system is performing an outdoor coil defrost operation.
System Protection
Cold Air Prevention (Heating mode with compressor running)
The system guards against discharging cold air in heating mode. It will delay the indoor fan until the evaporator coil has
warmed up to discharge warm, comfortable air into the room.
1) When the T
indoor
ambient < 750 F and the T
indoor
tube <= 1040 F with the fan in a stopped state, the indoor fan will begin
to run at low speed after a 2 minute delay. This will reduce cold air upon heating startup. Within 2 minutes, if
T
indoor
tube > 1040 F, the indoor fan will run at low speed. After 1 minute of operation, the fan will run at the preset fan
mode. Within 1 minute of low speed operation or 2 minutes of no fan operation, with the T
indoor
tube > 1080 F, the fan will
run at the preset mode.
2) If the T
indoor
ambient >= 750 F and the T
indoor
tube <= 1080 F the indoor fan will run at low speed for 1 minute than run
at the preset mode. After 1 minute of low speed operation, if the and the T
indoor
tube > 1080 F the fan will operate at its
preset mode.
Note:
The T
indoor
ambient in 1 & 2 above refers to the unit going into the heating mode, coming out of defrost.
Overcurrent and Speed Protection (
Total Current = I
total
)
The software will monitor the compressor current draw and adjust the compressor speed in order to maintain the inverter and
compressor in a safety and reliable operating range.
A. If I
total
<= 13, an increase or decrease in frequency will be allowed
B. If I
total
>13 and < 17, frequency will remain the same
C. If I
total
>= 17, the compressor will stop and the indoor fan will stop after 30 seconds
4)Fan Mode
Under this mode, the fan will run at the preset speed and the outdoor fan, compressor and 4-way valve will stop.
Basic Functions
Product Introduction
Summary of Contents for TERRA09HP230V1A
Page 13: ...13 Product Introduction Operation Characteristic Curve ...
Page 14: ...14 Product Introduction Capacity Variation Ratio According to Temperature ...
Page 16: ...16 Noise Criteria Curve Tables Product Introduction ...
Page 54: ...54 Electrical Schematics ...
Page 135: ...135 Gree Electric Appliances Inc C 2014 Cat No DFS TERRA HP 2SM Version 2 0 ...