36
Working Conditions and Range
●Rated Working Conditions of the whole Unit
Rated
working
condition
Indoor Side Status
Outdoor Side Status
Water Tank Temp.
Dry bulb
temp.
Wet bulb
temp.
Dry bulb
temp.
Wet bulb
temp.
Start Temp.
End Temp.
Rated Cooling
27
19
35
24
-
-
Rated Heating
20
15
7
6
-
-
Rated Cooling
and water
heating
27
19
35
24
15
55
Rated Heating
and water
heating
20
15
7
6
15
55
Rated Hot
Water
-
-
20
15
15
55
Note: 1.
The cooling / heating capacity and noise listed below are measured in factory.
2. The parameters below are measured under rated working conditions. In event of changes, the data provided on
nameplate shall prevail.
3.
The heating capacity of indoor unit is the heating capacity of heat pump, exclusive of the power of auxiliary electric
heater.
4.
The performance data below are measured according to Standard GB/T18837—2002.
●Operating temperature range
Cooling working range
Outdoor temperature -5
48
Heating working range
Outdoor temperature -20
27
Cooling and water heating working range
Outdoor temperature -5
43
Heating and water heating working range
Outdoor temperature -15
24
Heating water working range
Outdoor temperature -15
43
Summary of Contents for GMV-Pds100W/Na-K