Connection between Indoor and Outdoor Units
●
Capacity Code of Indoor and Outdoor Units
Capacity
Level
Capacity Code
Capacity Level
Capacity Code
Indoor Unit
Type 22
22
Type 63
63
Type 25
25
Type 71
71
Type 28
28
Type 80
80
Type 32
32
Type 90
90
Type 36
36
Type 100
100
Type 40
40
Type 112
112
Type 45
45
Type 125
125
Type 50
50
Type 140
140
Type 56
56
Outdoor Unit
Type 100
100
Type 120
120
Type 140
140
Type 160
160
☆
The sum of the capacity codes of indoor units and the Max number of indoor units may be selected
according to the following form.
Sum of Min. Indoor Unit Capacity
Sum of Max. Indoor
Unit Capacity
Max. number of
indoor units
GMV-Pds100W/Na-K
80
130
6
GMV-Pds120W/Na-K
80
130
6
GMV-Pds140W/Na-K
80
160
7
GMV-Pds160W/Na-K
80
160
7
☆
Selection of Y-type manifold pipe
Fig. 10
The Y-type Branching pipe may be selected from the following:
Total Capacity of
Downstream Indoor Units
Model
Y-type Branching Pipe
≤200
FQ01A/A
Connection between Indoor and Outdoor Units
Y-type manifold pipe