GREE DC Inverter Multi VRF System II Service Manual
94
11) Desynchronizing protection for inverter compressor
LED3 dual-8
nixie tube
displays P9
Whether the
sequence of wire
for compressor is
correct?
yes
Replace the main
board. Work
normally?
no
Replace
compressor
Work normally
yes
Adjust the
sequence of wire
for compressor
Whether
the wiring terminal
for compressor is
loose?
Connect the wires
of compressor
tightly
yes
no
no
Wired
controller
displays P0
12) Failure startup for inverter compressor
Wired
controller
displays P0
LED3 dual-8
nixie tube
displays PJ
Replace main
board. Work
normally?
Replace
compressor
Work normally
yes
no
Summary of Contents for GMV-100WL/A-T
Page 1: ...DC INVERTER VRF SYSTEM SERVICE MANUAL R410A...
Page 4: ...DC INVERTER VRF SYSTEM II SERVICE MANUAL R410A PRODUCT...
Page 16: ...GREE DC Inverter Multi VRF System II Service Manual 12 GMV 141WL C T...
Page 18: ...GREE DC Inverter Multi VRF System II Service Manual 14 CONTROL...
Page 64: ...GREE DC Inverter Multi VRF System II Service Manual 60 INSTALLATION...
Page 72: ...GREE DC Inverter Multi VRF System II Service Manual 68 DEBUGGING MAINTENANCE...
Page 173: ...JF00302323...