GREE DC Inverter Multi VRF System II Service Manual
144
1RWH
ķ
The refrigerant amount charged before delivery doesn’t include the amount that needs to be added
to indoor units and the connection pipeline.
ĸ
Length of connection pipe is decided on site. Therefore the amount of additional refrigerant shall be
decided on site according to the dimension and length of field-installed liquid pipe.
Ĺ
Record the amount of additional refrigerant for convenience of after-sales service.
2)
Calculation of the amount of additional refrigerant
Calculation method of the quantity of additional refrigerant (based on liquid pipe)
Quantity of additional refrigerant = ∑length of liquid pipe X quantity of additional refrigerant per meter
Quantity of additional refrigerant per meter for liquid pipe
˄
kg/m
˅
Φ
22.2
Φ
19.05
Φ
15.9
Φ
12.7
Φ
9.52
Φ
6.35
0.35
0.25
0.17
0.11
0.054
0.022
Note:First confirm that there is no leakage from the system. When compressor is not working, charge
additional R410a with specific amount to the unit through the filling opening of the liquid pipe valve
of the outdoor unit. If required amount cannot be quickly filled due to pressure increase of the pipe,
then set the unit in cooling startup and fill refrigerant from the low pressure check valve of the
outdoor unit.
3) Calculation
example
IDU
No.
IDU
ķ
IDU
ĸ
IDU
Ĺ
IDU
ĺ
Model
Duct type
GMV-ND72PL/B-T
Duct type
GMV-ND50PL/B-T
Duct type
GMV-ND36PL/B-T
Duct type
GMV-ND25PL/B-T
Liquid pipe:
No.
A
B
C
D
Pipe size
Φ
9.52
Φ
9.52
Φ
9.52
Φ
6.35
Length
10m
5m
5m
5m
No.
a
b
c
d
Pipe size
Φ
9.52
Φ
6.35
Φ
6.35
Φ
6.35
Length
3m
3m
2m
1m
Total length of each liquid pipe
Φ
9.52
˖
A+B+C+a=10+105+5+3=23m
Φ
6.35: D+b+c+d=5+3+2+1=11m
The minimum quantity of additional refrigerant = 23×0.054+11×0.022
˙
1.484kg
Summary of Contents for GMV-100WL/A-T
Page 1: ...DC INVERTER VRF SYSTEM SERVICE MANUAL R410A...
Page 4: ...DC INVERTER VRF SYSTEM II SERVICE MANUAL R410A PRODUCT...
Page 16: ...GREE DC Inverter Multi VRF System II Service Manual 12 GMV 141WL C T...
Page 18: ...GREE DC Inverter Multi VRF System II Service Manual 14 CONTROL...
Page 64: ...GREE DC Inverter Multi VRF System II Service Manual 60 INSTALLATION...
Page 72: ...GREE DC Inverter Multi VRF System II Service Manual 68 DEBUGGING MAINTENANCE...
Page 173: ...JF00302323...