PRODUCT
5�2 Piping diagram of GMV-Pdm335W/NaB-M,GMV-Pdm400W/NaB-M,GMV-Pdm450W/NaB-M
(1)
(3)
(5)
(7)
(8)
(9)
(18)
(20)
(19)
(13)
(21)
(14)
(15)
(16)
(17)
(27)
(28)
(26)
(29)
(24)
(23)
(22)
(25)
(12)
(11)
(10)
(6)
(6)
(4)
(4)
(2)
(2)
NO.
Name
Major Function
1
Inverter compressor(INV)
According to the actual need, the inverter compressor
can adjust its revolution among 30rps~90rps.
2
Standard compressor(STD1/STD2)
When the inverter compressor fails to meet the needs of the
system, the fixed-frequency compressor will start together.
3
High pressure switch(for INV)
When the discharge pressure of the inverter compressor
exceeds the upper limit of the high pressure switch,
a feedback signal will be sent out to stop the unit
immediately so as to protect the compressor.
4
High pressure switch(for STD1/ STD2)
When the discharge pressure of the fixed-frequency
compressor exceeds the upper limit of the high pressure
switch, a feedback signal will be sent out to stop the
unit immediately so as to protect the compressor.
5
Check valve(for INV)
It is used to prevent the high-pressure reverse gas going into the
inverter compressor at the moment that the compressor stops
so as to avoid abnormal startup next time and other problems.
Summary of Contents for CN851W1000
Page 1: ...DCINVERTERMULTIVRFSERVICEMANUAL T1 R410A 50Hz GC201107 CENTRAL AIR CONDITIONERS ...
Page 6: ...DC Inverter Multi VRF Service Manual 1 PRODUCT PRODUCT ...
Page 24: ...DC Inverter Multi VRF Service Manual 19 CONTROL CONTROL ...
Page 92: ...DC Inverter Multi VRF Service Manual 87 INSTALLATION ...
Page 146: ...DC Inverter Multi VRF Service Manual 141 ENGINEERING DEBUGGING ...
Page 171: ...166 DC Inverter Multi VRF Service Manual MAINTENANCE ...
Page 233: ...JF00300207 ...