PRODUCT
4 PRODUCT DATA
4�1 Product Data of Outdoor Unit
Model(Combined unit)
—
—
—
Model
GMV-Pdm224W/NaB-M
GMV-Pdm280W/NaB-M
GMV-Pdm335W/NaB-M
Capacity
Cooling
kW
22.4
28
33.5
kBtu/h
76.43
95.536
114.302
Heating
kW
25
31.5
37.5
kBtu/h
85.3
107.478
127.95
Sound Pressure Level
dB(A)
58
58
60
Power Supply
V/Hz/Ph
380-415V~50Hz-3Ph
Power input
Cooling
kW
5.52
7.52
9.23
Heating
kW
5.82
7.7
9.38
Current
Cooling
A
9.87
13.44
16.50
Heating
A
10.4
13.76
16.77
Circuit breaker
A
32
32
40
Recommended
Power Lines
mm
2
×N
6×5
6×5
10×5
Moisture protection
IP24
IP24
IP24
Climate Type
T1
T1
T1
Connecting
pipe
Gas Pipe
mm
Φ22.2
Φ22.2
Φ28.6
Inch
7/8
7/8
9/8
Liquid
Pipe
mm
Φ9.52
Φ9.52
Φ12.7
Inch
3/8
3/8
1/2
Oil Pipe
mm
—
—
—
Inch
—
—
—
Connection Method
Brazing Connection
Brazing Connection
Brazing Connection
Dimensions
of Unit
Width
mm
930
930
1340
Depth
mm
770
770
770
Height
mm
1670
1670
1670
Dimensions
of Package
Width
mm
1010
1010
1420
Depth
mm
850
850
850
Height
mm
1850
1850
1850
Net Weight
kg
255
255
350
Gross Weight
kg
275
275
380
Loading Quantity
( 20’ Container )
unit
12
12
7
Loading Quantity
( 40’ Container )
unit
24
24
16
Loading Quantity ( 40’
High Cube Container )
unit
24
24
16
Notes:
① .
The sound level is tested under circumstance of semi-anechoic chamber; the value of noise could be a little
higher in actual operation.
② .
The data will change with the change of products. Refer to those parameters listed on nameplate.
③ .
The charge amount of refrigerant in the list is the datum when there is not drop height vertically between
indoor unit and outdoor unit, without consideration of connection pipe. So calculate the additional charge amount
according to actual condition during installation.
④ .
Section area of lead wire is only applicable for 15-m distance.If above, increase the section area to avoid
overload of current which would cause burnout of lead wire.
⑤ .
The outdoor fan of this unit is without static pressure.If static pressure is required, please specially notice it on
purchase order.
⑥ .
Running condition of cooling: outdoor temperature -5 ~48 ; Running condition of heating: outdoor
temperature -20 ~27 .
Summary of Contents for CN851W1000
Page 1: ...DCINVERTERMULTIVRFSERVICEMANUAL T1 R410A 50Hz GC201107 CENTRAL AIR CONDITIONERS ...
Page 6: ...DC Inverter Multi VRF Service Manual 1 PRODUCT PRODUCT ...
Page 24: ...DC Inverter Multi VRF Service Manual 19 CONTROL CONTROL ...
Page 92: ...DC Inverter Multi VRF Service Manual 87 INSTALLATION ...
Page 146: ...DC Inverter Multi VRF Service Manual 141 ENGINEERING DEBUGGING ...
Page 171: ...166 DC Inverter Multi VRF Service Manual MAINTENANCE ...
Page 233: ...JF00300207 ...