DC Inverter Multi
VRF Service Manual
203
5 FEATURES OF THE HIGHT/LOW PRESSURE SENSORS
5�1 Features of the High Pressure Sensors (R410a)
Temp.(
)
Absolute Pressure(kPa)
Volt. (V)
Temp. (
)
Absolute Pressure(kPa)
Volt. (V)
-40
176
0.102
16
1300
1.300
-39
184
0.111
17
1337
1.340
-38
193
0.120
18
1375
1.380
-37
202
0.130
19
1413
1.421
-36
211
0.139
20
1453
1.463
-35
220
0.149
21
1493
1.506
-34
230
0.160
22
1535
1.551
-33
240
0.170
23
1577
1.596
-32
250
0.181
24
1620
1.641
-31
261
0.193
25
1664
1.688
-30
273
0.206
26
1708
1.735
-29
283
0.216
27
1754
1.784
-28
295
0.229
28
1801
1.834
-27
307
0.242
29
1848
1.884
-26
319
0.255
30
1897
1.937
-25
332
0.268
31
1946
1.989
-24
345
0.282
32
1996
2.042
-23
359
0.297
33
2048
2.098
-22
373
0.312
34
2100
2.153
-21
388
0.328
35
2153
2.210
-20
403
0.344
36
2208
2.268
-19
418
0.360
37
2263
2.327
-18
434
0.377
38
2320
2.388
-17
450
0.394
39
2377
2.448
-16
467
0.412
40
2436
2.511
-15
484
0.430
41
2495
2.574
-14
502
0.450
42
2556
2.639
-13
520
0.469
43
2618
2.705
-12
538
0.488
44
2681
2.772
-11
558
0.509
45
2745
2.841
-10
577
0.530
46
2810
2.910
-9
597
0.551
47
2876
2.980
-8
618
0.573
48
2944
3.053
-7
639
0.596
49
3013
3.126
-6
661
0.619
50
3083
3.201
-5
684
0.644
51
3154
3.277
-4
707
0.668
52
3226
3.353
-3
730
0.693
53
3300
3.432
-2
754
0.718
54
3374
3.511
-1
779
0.745
55
3450
3.592
0
804
0.772
56
3528
3.675
1
830
0.799
57
3606
3.759
2
857
0.828
58
3686
3.844
3
884
0.857
59
3767
3.930
4
912
0.887
60
3849
4.018
5
940
0.917
61
3932
4.106
Summary of Contents for CN851W1000
Page 1: ...DCINVERTERMULTIVRFSERVICEMANUAL T1 R410A 50Hz GC201107 CENTRAL AIR CONDITIONERS ...
Page 6: ...DC Inverter Multi VRF Service Manual 1 PRODUCT PRODUCT ...
Page 24: ...DC Inverter Multi VRF Service Manual 19 CONTROL CONTROL ...
Page 92: ...DC Inverter Multi VRF Service Manual 87 INSTALLATION ...
Page 146: ...DC Inverter Multi VRF Service Manual 141 ENGINEERING DEBUGGING ...
Page 171: ...166 DC Inverter Multi VRF Service Manual MAINTENANCE ...
Page 233: ...JF00300207 ...