DC Inverter Multi
VRF Service Manual
189
2�11 PFC Protection
Yes
Yes
Yes
No
No
No
No
Yes
E5 is displayed on
the wired controller
PFC abnormal
Hc is displayed
Monitoring
display
Nixie tube of
mainboar d
It is recorded
Is it wet,dirty or
short-circuit?
Inspect the mainboar d 1 min
af ter powe r off or the buss
voltage is below 36V
Dry, and clean it or
remove short circuit.
Restart the unit.
circuit work work ?
1. If it is affected by damp, find out the
reason and take some precautionary
measures. After drying the mainboard
,
brush it with damp proof gum water
.
2. If it is polluted, find out the reason
and protect it from dust . If the
environment is bad , clean the dirt
periodically.
3. If it is short-circuit, find out the
reason and clean the electric box so
as to prevent the conductive matter
such as iron chippings adhering on
the board
.
Is + 15V
of mainboard stable?
15VA-pin 1,2
Is IPM
module of mainboard
damaged?
Replace mainboard