DC Inverter Multi
VRF Service Manual
97
4 INSTALLATION REQUIREMENTS OF REFRIGERANT PIPING
4.1 Specification
R410a refrigerant system
External Diameter(mm/inch)
Thickness(mm)
External Diameter(mm/inch)
Thickness(mm)
φ6.35
0.8
φ25.4
1.5
φ9.52
0.8
φ28.6
1.5
φ12.7
1
φ34.9
1.5
φ15.9
1
φ41.3
2.0
φ19.05
1
φ44.5
2.0
φ22.2
1.5
φ54.1
2.0
4�2 Allowable Length and Height Differences of the Refrigerant Piping between the Indoor and Outdoor Units
Height dif
ference between indoor unit and outdoor unit:
H
The 1st
branch section
Equivalent length of farthest pipe: L
The equivalent length of the farthest pipe from the 1st branch: L
The equivalent length is 0.5m for each Y-type branch pipe.
Outdoor unit
Indoor unit
Height dif
ference
between indoor units:
H
L1
L2
L3
L4
L5
L6
L7
L8