177
Motor and fan
Precondition: The power supply has been disconnected.
Step
Diagram
Operation Procedure
(5) Remove the
motor.
Remove the motor from the
support and remove the
centrifugal fan from the motor
axle. Then, remove the motor.
For motors that are
accompanied with supports,
the supports need removing as
well.
(6) Install a new
motor.
Assemble units based on the
reverse order of this procedure
and power on the units for test.
GMV-ND72PH/B-T(U) / GMV-ND96PH/B-T(U)
Motor and fan
Precondition: The power supply has been disconnected.
Step
Diagram
Operation Procedure
(1) Remove the
line
connecting to
the motor.
Use a screwdriver to unscrew
the electric box cover.
Remove from the master board
the line connecting to the
motor and remove the tie.
(2) Disassemble
the seal plate
and cover
plate.
Use a screwdriver to unscrew
the seal plate and cover plate
and then remove them.
(3) Remove the
grille
Use a screwdriver to unscrew
the cover plate component.
(4) Remove the
centrifugal
fan.
Use a screwdriver to unscrew
the front volute casing and
then remove the volute casing.
Summary of Contents for CM100N1480
Page 7: ...GREE Multi Variable Air Conditioners Indoor Unit 1 PRODUCT...
Page 51: ...GREE Multi Variable Air Conditioners Indoor Unit 45 CONTROL...
Page 52: ...GREE Multi Variable Air Conditioners Indoor Unit 46 CHAPTER 2 CONTROL 1 Operation Flowchart...
Page 95: ...GREE Multi Variable Air Conditioners Indoor Unit 89 INSTALLATION...
Page 139: ...GREE Multi Variable Air Conditioners Indoor Unit 133 MAINTENANCE...
Page 238: ...GREE Multi Variable Air Conditioners Indoor Unit 232 GMV ND30G B4B T U GMV ND36G B4B T U...
Page 266: ...JF00302921...