GREE
Multi Variable Air Conditioners Indoor Unit
84
Query Code
Query Content
Query Sub-item
Level 2 Query Content
C11
Indoor unit quantity query in one-to-many control mode
C12
Temperature query for outdoor environment temperature sensor
C13
CAN2 bus line ID query
C14
Inlet-tube temperature query of IDU
C15
Outlet temperature query of IDU
C16
Opening degrees query of electronic expansion valve of IDU
n2
Capacity configuration ratio upper-limit query of outdoor and IDUs
n4
Highest capacity output limitation query
n6
Historical fault query ingress of ODU
01
Fault 1
02
Fault 2
03
Fault 3
04
Fault 4
05
Fault 5
A6
Unit cooling/heating function
A7
Outdoor silent mode
4.4.3 Parameter Settings
For parameter settings, users can set user parameters and engineering parameters of the unit. The
parameter setting method is as follows:
(1) After entering parameter query, switch the query code to "C00". Press and hold "
" for
five seconds to enter the parameter setting status. The setting text is displayed and "P00"
blinks in the temperature area.
(2) Press "
" to switch the setting code and select a unit parameter to be set (see Table 2.6 for
(3) parameters that can be set.
(4) Press "
" to enter parameter settings. The current parameter value blinks in the timer
area. Press "
" to change the parameter value.
(5) Press "
" to confirm query and return to step 2.
(6) After entering engineering commissioning, the system automatically quits the engineering
commissioning status if no valid operations are performed within 20 seconds. To directly quit
the engineering commissioning status, press "
".
Table 2.6 Setting Parameters
Setting
Code
Setting Content
Setting Value
P00
Invalid
P10
Master IDU settings
00: not changing the current settings
01: setting the corresponding IDU to master IDU
001-255: setting the IDU corresponding to *** to master IDU
P15
Power-down memory mode
settings
00: standby after power-down recovery
01: restoring the original status after power-down recovery
P17
Historical fault clearing
00: not cleared
01: cleared
Summary of Contents for CM100N1480
Page 7: ...GREE Multi Variable Air Conditioners Indoor Unit 1 PRODUCT...
Page 51: ...GREE Multi Variable Air Conditioners Indoor Unit 45 CONTROL...
Page 52: ...GREE Multi Variable Air Conditioners Indoor Unit 46 CHAPTER 2 CONTROL 1 Operation Flowchart...
Page 95: ...GREE Multi Variable Air Conditioners Indoor Unit 89 INSTALLATION...
Page 139: ...GREE Multi Variable Air Conditioners Indoor Unit 133 MAINTENANCE...
Page 238: ...GREE Multi Variable Air Conditioners Indoor Unit 232 GMV ND30G B4B T U GMV ND36G B4B T U...
Page 266: ...JF00302921...