contact local dealer to arrange professional technicians for the installation.
3
Do not connect power until all installation work is finished.
3.9.3 Installation Notice
The unit shall be installed by the professional personnel according to this installation instruction
to ensure proper use.
Please contact the local Gree appointed service center before installation. Any malfunction
caused by the unit that is not installed by the Gree appointed service center would probably not
be dealt with on time because of the inconvenience of the business contact.
It should be guided under the professional personnel when the air conditioner unit is moved to
other place.
3.9.4 Selection of Air Switch and Power Cord
Model
Power Cord Size
Air Switch
apacity
(A)
Minimum Sectional
Area of
Ground Wire
(mm
2
/AWG)
Minimum Sectional
Area of Power
Cord
(mm
2
/AWG)
GMV-NDX42P/A-T(U)
208/230V/60Hz
15
1.0/AWG18
1.0/AWG18
GMV-NDX48P/A-T(U)
208/230V/60Hz
15
1.0/AWG18
1.0/AWG18
GMV-NDX54P/A-T(U)
208/230V/60Hz
15
1.0/AWG18
1.0/AWG18
GMV-NDX72P/A-T(U)
208/230V/60Hz
15
1.0/AWG18
1.0/AWG18
GMV-NDX96P/A-T(U)
208/230V/60Hz
15
1.0/AWG18
1.0/AWG18
3.10 Installation of Compact Four-way Cassette Type Indoor Unit
3.10.1 Outline and installation dimension
Bottom
face
of
ceiling
S
us
pe
ns
io
n
bo
lt
pi
tc
h
E
F
B
C
D
A
Panel external dimension
Unit: mm(inch)
Model
A
B
C
D
E
F
GMV-ND07T/B-T(U)
GMV-ND09T/B-T(U)
GMV-ND12T/B-T(U)
GMV-ND15T/B-T(U)
GMV-ND18T/B-T(U)
670
(26-3/8)
596
(23-1/2)
592
(23-5/16)
571
(22-1/2)
145
(5-11/16)
240
(9-1/2)
Summary of Contents for CM100N1480
Page 7: ...GREE Multi Variable Air Conditioners Indoor Unit 1 PRODUCT...
Page 51: ...GREE Multi Variable Air Conditioners Indoor Unit 45 CONTROL...
Page 52: ...GREE Multi Variable Air Conditioners Indoor Unit 46 CHAPTER 2 CONTROL 1 Operation Flowchart...
Page 95: ...GREE Multi Variable Air Conditioners Indoor Unit 89 INSTALLATION...
Page 139: ...GREE Multi Variable Air Conditioners Indoor Unit 133 MAINTENANCE...
Page 238: ...GREE Multi Variable Air Conditioners Indoor Unit 232 GMV ND30G B4B T U GMV ND36G B4B T U...
Page 266: ...JF00302921...