Removal of Fan Motor
Remark: before removing, making sure power is disconnected.
Step
Diagram
Operation Procedure
(6) Remove
reversion
loop and
centrifugal
blade.
Remove 4 screws fixing the
reversion loop and then remove
the reversion loop’ remove nuts
on blade and then remove the
centrifugal blade.
4.6 High Static Pressure Duct Type Indoor Unit
NOTICE!
The following steps are specific for GMV-ND18PHS/A-T(U) units. For other units, the
assembly and disassembly procedure is similar except the specifications of centrifugal fans and motors.
Motor and fan
Precondition: The power supply has been disconnected.
Step
Diagram
Operation Procedure
(1) Remove the
line
connecting to
the motor.
Use a screwdriver to unscrew
the electric box cover.
Remove from the master board
the line connecting to the
motor and remove the tie.
(2) Disassemble
the seal plate
and cover
plate.
Use a screwdriver to unscrew
the seal plate and cover plate
and then remove them.
(3) Remove the
cover plate
component.
Use a screwdriver to unscrew
the cover plate component.
Summary of Contents for CM100N1480
Page 7: ...GREE Multi Variable Air Conditioners Indoor Unit 1 PRODUCT...
Page 51: ...GREE Multi Variable Air Conditioners Indoor Unit 45 CONTROL...
Page 52: ...GREE Multi Variable Air Conditioners Indoor Unit 46 CHAPTER 2 CONTROL 1 Operation Flowchart...
Page 95: ...GREE Multi Variable Air Conditioners Indoor Unit 89 INSTALLATION...
Page 139: ...GREE Multi Variable Air Conditioners Indoor Unit 133 MAINTENANCE...
Page 238: ...GREE Multi Variable Air Conditioners Indoor Unit 232 GMV ND30G B4B T U GMV ND36G B4B T U...
Page 266: ...JF00302921...